Installation Guide
www.stiebel-eltron-usa.com Accelera® 220-300 E | 5
ENGLISH
14˝
(0.4 m)
2´ (0.6 m)
8˝ (0.2 m)
6´ (1.8 m)
Air flow
intake
Air flow
intake
Air flow
exhaust
Air flow
exhaust
2´ (0.6 m)
Air flow
intake
Air flow
exhaust
6´ (1.8 m)
Minimum room volume:
800 ft
2
, 10´ x 10´ x 8´
(22.7 m
2
, 3 m x 3 m x 2.4 m)
Acceptable positioning, vent parallel to a wall:
Acceptable positioning, vent parallel to a wall in a corner:
2´
(0.6 m)
2´
(0.6 m)
8˝ (0.2 m)
8˝
(0.2 m)
6´
(1.8 m)
42˝ (220 E)
60˝ (300 E)
› Do not install in a room
with less than 800 cubic
feet of total volume.
› Do not install with the air
exhaust pointing at a wall
or any surface closer than
6 feet away.
› Do not install with the air
intake pointing to a wall or
any surface closer than 2
feet away.
› If you are installing an
Accelera 220 E next to
another appliance, the
appliance cannot be
taller than 42. If you are
installing an Accelera 300
E, the appliance cannot
be taller than 60. This
restriction is to prevent an
appliance from obstructing
air fl ow to and from the
Accelera.
› Failure to follow
installation instructions
will void the factory
warranty.
QUICK START-UP GUIDE
Required room dimensions and clearances