Precautions for installation
The supply voltage at the reader’s connector should be between +7 Vdc and +28 Vdc.
As far as possible, keep the reader away from computer or power source cables. They can generate electrical interference, depending on their radiation level
and the proximity of the reader.
Recommended distance between two readers: parallel plane: 11.8 in same plane: 15.8 in perpendicular plane: 9.8 in.
Readers installed on a metal surface may have reduced performances.
Use a ferrite (two-way) for the cable (power supply and data). Example: reference 74271222 WURTH ELEKTRONIK.
By design, the reader can be installed indoors and outdoors.
Connect the wires or the connector of the reader BEFORE powering on.
Operating temperature:
Temperature
-22 °F to 158 °F
-30°C to +70°C
-22 °F to 140 °F
-30°C to +60°C
-4 °F to 158 °F
-20°C to +70°C
-4 °F to 140 °F
-20°C to +60°C
14 °F to 122 °F
-10°C to +50°C
Readers
A, B
AQ, BQ
C, I, J, K
CQ
D, E, F
TTL pull-ups
For data signals, 10k pull-up resistors are connected internally to V
in
(power supply voltage) for optimal wiring distances.
RS232 / RS485 communication
Bus architecture (RS485)
Wiring resistors R1 and R2 use extended features of the RS485 bus: FAIL-SAFE (see RS485-AN-960).
R1 & R2: 1.5 kresistor supplied.
R
T
: 120 Ω end-of-line resistor supplied
Smart mounting plate dimensions
Version 1 Version 2
General tolerance following ISO NFT 58-000 standard.
Scalability
Scalability is a specific feature of the Architect® series.
Each reader is composed of three parts: one switchable
cover, one RFID core and one smart mounting plate.
You can upgrade functionalities and security levels by
switching the cover and/or adding a biometric, 125kHz
or QR Code module.
Available Baud rate
9600, 19200, 38400, 57600, 115200 bauds
Factory Baud rate
ARC R & S: 9600; ARC W: 38400 (SSCP), 9600 (OSDP
TM
)
Mode
Asynchronous
Number of bits
8
Transfer mode
LSB first
Stop bit
1
RS485
Default broadcast address 00h
US
FR
ES
More details about reader
communication are available
in the protocol specification