User guide
4
Table 1 – Performance and Specifi cation Data – Separated Combustion Blower Unit Heater
Unit Size 100 125 150 175 200 225 250 300 350 400
PERFORMANCE DATA ‡
Input BTU/Hr 100,000 125,000 150,000 175,000 200,000 225,000 250,000 300,000 350,000 400,000
(kW) (29.3) (36.6) (43.9) (51.2) (58.6) (65.9) (73.2) (87.8) (102.5) (117.1)
Output BTU/Hr 80,000 100,000 120,000 140,000 160,000 180,000 200,000 240,000 280,000 320,000
(kW) (23.4) (29.3) (35.1) (41.0) (46.9) (52.7) (58.6) (70.3) (82.0) (93.7)
Thermal Effi ciency (%) 80 80 80 80 80 80 80 80 80 80
Free Air Delivery CFM 1,200 1,575 1,975 2,300 2,400 2,600 2,850 3,950 4,600 4,800
(cu. m/s) (0.566) (0.743) (0.932) (1.086) (1.133) (1.227) (1.345) (1.864) (2.171) (2.266)
Air Temperature Rise Deg. F. 62 59 56 56 62 64 65 56 56 62
(Deg. C) (34) (33) (31) (31) (34) (36) (36) (31) (31) (34)
Outlet Velocity FPM 880 950 1030 1045 965 935 930 1080 1090 1000
(m/s) (4.47) (4.83) (5.23) (5.31) (4.90) (4.75) (4.72) (5.49) (5.54) (5.08)
Full Load Amps at 115V 8.3 9.8 10.6 10.6 15.2 15.2 15.2 15.2 18.6 18.6
MOTOR DATA: Motor HP 1/4 1/3 1/2 1/2 3/4 3/4 3/4 3/4 1 1
Motor (kW) (0.19) (0.25) (0.37) (0.37) (0.56) (0.56) (0.56) (0.56) (0.75) (0.75)
Motor Type SPH SPH SPH SPH SPH SPH SPH SPH cap.start cap.start
R.P.M. 1725 1725 1725 1725 1725 1725 1725 1725 1725 1725
Amps @ 115V 5.1 6.6 7.4 7.4 12.0 12.0 12.0 12.0 15.4 15.4
DIMENSIONAL DATA in. (mm)
“A” Height to Top of Unit 31-1/4 31-1/4 36-1/4 36-1/4 36-1/4 36-1/4 36-1/4 36-1/4 36-1/4 36-1/4
(794) (794) (921) (921) (921) (921) (921) (921) (921) (921)
“B” Height to Top of Hanger 34-1/16 34-1/16 39-1/16 39-1/16 39-1/16 39-1/16 39-1/16 39-1/16 39-1/16 39-1/16
(865) (865) (992) (992) (992) (992) (992) (992) (992) (992)
“C” Hanging Distance Width 14-3/4 17-1/2 17-1/2 20-1/4 23 25-3/4 28-1/2 34 39-1/2 45
(375) (444) (444) (514) (584) (654) (724) (864) (1003) (1143)
“D” Discharge Opening Width 15-3/8 18-1/8 18-1/8 20-7/8 23-5/8 26-3/8 29-1/8 34-5/8 40-1/8 45-5/8
(391) (460) (460) (530) (600) (670) (740) (879) (1019) (1159)
“E” Width of Unit 17-7/8 20-5/8 20-5/8 23-3/8 26-1/8 28-7/8 31-5/8 37-1/8 42-5/8 48-1/8
(454) (524) (524) (594) (664) (733) (803) (943) (1083) (1222)
“F” to Centerline of Flue 5-7/8 7-1/4 7-1/4 8-5/8 10 11-1/4 12-3/4 15-1/2 18-1/4 21
(149) (184) (184) (219) (254) (286) (324) (394) (464) (533)
“G” Hanging Distance Depth 18-1/2 18-1/2 18-1/2 20 20 23 23 23 23 23
(470) (470) (470) (508) (508) (584) (584) (584) (584) (584)
“H” Depth to Rear of Housing 42-3/4 44-3/8 44-3/8 47-3/16 47-3/16 50-7/8 48 50-7/8 50-7/8 51
(1086) (1127) (1127) (1199) (1199) (1292) (1219) (1292) (1292) (1295)
Flue Size Dia-in.** 4 4 4 4 5 5 5 6 6 6
(Dia-mm) (102) (102) (102) (102) (127) (127) (127) (152) (152) (152)
Air Inlet Size-in. 4 4 4 4 5 5 5 6 6 6
(mm) (102) (102) (102) (102) (127) (127) (127) (152) (152) (152)
Blower Size-in. 9 10 10 12 12 12 12 (2)10 (2)12 (2)12
Gas Inlet-Natural Gas-in. 1/2 1/2 1/2 1/2 1/2 3/4 3/4 3/4 3/4 3/4
Gas Inlet-LP Gas-in. 1/2 1/2 1/2 1/2 1/2 ← 1/2 or 3/4 →
Approx. Shipping Wt. lb. 298 330 362 394 426 458 490 558 618 678
(kg) (135) (150) (164) (179) (193) (208) (222) (253) (280) (308)
DIMENSIONS .XXX STANDARD UNITS
DIMENSIONS IN PARENTHESIS (XXX) MILLIMETERS
Figure 2
‡ Ratings shown are for unit installations at elevations between 0 and 2000 ft. (610m). For unit installations in USA above 2000 ft. (610m), the unit input must be derated 4% for each
1000 ft. (305m) above sea level; refer to local codes, or in absence of local codes, refer to the latest edition of the National Gas Code, ANSI Standard Z223.1 (N.F.P.A. No. 54).
For installations in Canada, any references to deration at altitudes in excess of 2000 ft. (610m) are to be ignored. At altitudes of 2000 to 4500 ft. (610m to 1372m), the unit must be
derated to 90% of the normal altitude rating, and be so marked in accordance with the ETL certifi cation.
LEGEND: SPH = SPLIT PHASE
CAP. START = CAPACITOR START