- Sterling Air Coole Protable Water Chillers Operation and Installation Manual

SMC Series Chillers Page 27
Figure 12: Typical SMC Series E5CK Microprocessor Controller
PV
SV
OUT1
OUT2 MANU STOP RMT AT SUB1
AT
E5CK
OMRON
OUT2 LED
The orange OUT2 energizes whenever the process temperature is two degrees (2°F/ºC)
or more above the To Process set point. The compressor then comes on and runs until
the temperature at the To Process thermocouple is two degrees (2°F/ºC) below the set
point.
This +2°F/ºC control set point is factory-set for proper compressor operation. Changing
it is not recommended without consulting the AEC Service Department.
MANU LED
The orange MANU LED does not light because it is not used.
STOP LED
The orange
STOP LED does not light because it is not used.