- Sterling Air Coole Protable Water Chillers Operation and Installation Manual
SMC Series Chillers Page 25
4-4 SMC Water Circuit Pressure Drop Table
Model Gallons per minute Liters per minute
ΔP (psig) ΔP (kPa)
SMC050
2.0 7.5 2.5 17.3
2.4 9.0 4.0 27.6
3.6 13.6 7.5 51.8
4.8 18.1 12.5 86.2
SMC100
2.0 7.5 2.5 17.3
2.4 9.0 2.5 17.3
3.6 13.6 3.0 20.7
4.8 18.1 5.0 34.5
SMC150
2.0 7.5 2.5 17.3
2.4 9.0 2.5 17.3
3.6 13.6 3.0 20.7
4.8 18.1 3.5 24.2