User guide

Page 42 Royal Series Water Temperature Control Units
6-5 Safety Devices
Caution!
Make sure that only qualified electricians test safety devices!
Safety devices should be tested for function every six (6) months.
Perform the following procedures for testing:
Motor Overload
Disconnect main power. Open the electrical enclosure and rotate
the manual TEST button on the motor overload to the tripped
position. Close the enclosure and reconnect main power. Push the
START button. The unit should not start and the Pump Overload
indicator should illuminate.
Press the RESET button. The unit is now ready for operation.
Pressure Switch
With the unit running, program a set point of 30ºF (-1ºC). Allow
the process temperature to drop under 100ºF (38ºC). When the
process temperature reaches that point, turn off the water supply.
The pump should stop and the Low Water Pressure indicator
should illuminate. Turn the water supply on to reset the pressure
switch.
Adjusting the Pressure Switch
The pressure switch used in your Royal Series water temperature
control unit is factory set at 16 psig (110.3 kPa/1.1 bars). However,
if the process does not require the unit to operate at 250ºF (121ºC),
you can adjust the switch to meet your process needs.
Tools Required
• Small flat blade screwdriver
• #2 Phillips head screwdriver