Owner's manual

MICRO Series Water Temperature Control Units Page 7
1-3 Models Covered
This manual provides operation, installation, and maintenance instructions for the
MICRO Series water temperature control unit.
Model numbers are listed on the serial tag. Make sure that you know the model
number, serial number, and operating voltage of your temperature control unit if
you contact the manufacturer.
1-4 Standard MICRO Series Features
Compact, rugged cabinet with easy-access side panels
Non-ferrous construction
Incoloy™ immersion heaters with IEC contactors
NEMA 1 electrical enclosure
CAL 9000 microprocessor controller with fuzzy logic; includes status lights; CE
and
C
UL
Independent high temperature safety thermostat
Motor Circuit Protector for pump
¼” cooling solenoid valve
EPDM/Carbon-carbide pump seal
Adjustable low supply water pressure switch; factory-set at 16 psig (110 kPa/1.1
bars)
150 psig (1,034 kPa/10.3 bars) pressure relief valve
Choice of 208, 230 or 460 operating voltages
¾” water supply and drain connections; ¾” process connections
Automatic vent sequence
Operating range of 0ºF to 250ºF (-17ºC to 121ºC)
One (1) -year parts and labor warranty at the factory; three (3) -year controller
warranty
1-5 Available Options
MICRO Series systems are available with options to tailor the unit to your
requirements. Some are factory installed; some can be retro-fitted in the field.
Consult your manufacturer sales representative for more information. Available
MICRO Series options include:
RS-232 or RS-485 communications
Remote controller enclosure
Heaters available in 3 kW, 6 kW, and 9 kW
Quick Cool function