Owner manual

GC Series Central Chillers Chapter 2: Functional Description 11 of 79
determined from a PID algorithm using a discharge pressure transducer as the process
variable. The VFD or water regulating valve is controlled from the analog output to an
adjustable discharge pressure setpoint. The analog output starts at the initial “discharge
pressure start” % for a given time delay (discharge pressure hold). After the time delay, it
will control to the discharge pressure setpoint via the PID control. There is also a setting to
control the discharge pressure to the most efficient value.
2-3 Standard Features
Mechanical Features
Compressor Hermetic scroll compressors.
EvaporatorStainless steel copper brazed plate evaporators.
Water-Cooled CondenserShell-and-tube condensers. All come with electronic cooling
water regulating valves.
Remote Air-Cooled CondenserAluminum microchannel with low ambient control down
to
20ºF (-29ºC) via variable-speed fan(s).
PipingNon-ferrous chilled water piping
Other Mechanical Features
Low process water thermal flow switch
NEMA-rated fan motor(s) on remote air-cooled condenser models
Galvanized structural steel frame, polyester powder coat painted electrical enclosure
Fully insulated refrigeration and process water piping
20 mesh strainer in the evaporator
Electrical Features
Fully accessible NEMA 4-style electrical control enclosure
Single-point power and ground connection per module
Non-fused disconnect switch, lockable per module
Branch circuit protection per module
208-230/3/60 (not available on GC140-210), 380-460/3/60, 575/3/60 volt; 380-
415/3/50 volt
Refrigeration Features
HFC-410a refrigerant
High refrigerant pressure cutout switch (manual reset)
Suction and discharge pressure transducers.
High refrigerant pressure spring actuated relief valve
Multiple refrigeration access ports
Liquid line shut-off ball valves