AccuMeter Controller Chapter 11: Configuring a new PLC 75
ALARM PAGE Tab
NO FLOW ALARM ENABLED/DISABLED. This alarm is generated if the blender is
running and the extruder is not taking material away. This could happen if a bridge forms
directly over the feed throat.
NO FLOW TIME (SECONDS). This is the sample time that is used to determine if a NO
FLOW condition exist. Entering “0” will disable the alarm.
NO FLOW BITS. This is the number of weight bits that must pass during the NO FLOW
TIME (SECONDS) in order for the system to determine that there is flow.
CANNOT ACHIEVE RATE ALARM ENABLED/DISABLED. This alarm should remain
disabled and will be removed in future versions. The NO MATERIAL alarm will supersede
this alarm.
NO MATERIAL ALARM ENABLED/DISABLED. This alarm is generated if the mass flow’s
weight is every below the EMPTY % (Hopper Setup Tab). When you first start the blender
there is a 30 second delay to allow the blender to get primed.
LOADCELL ALARM ENABLED/DISABLED. This alarm occurs if either the loadcell is
disconnected or is mechanically negative sprung (reading negative). If you disconnect a
loadcell the CURRENT BITS (Calibrate Scale page) will go to 32767. This alarm will not
detect a non-linear or damaged loadcell and is not intended to replace standard scale calibration
and testing procedures.