User guide

AccuMeter Controller Chapter 5: Programming a New PLCs IP address 41
20. It is also important to test that it has been disabled. First clear the history by touching the “Clear
History” button. Next reboot the Compact Logix PLC. Check to make sure that you do not see
any request in the “History” window. If you do then repeat the disabling procedure as mentioned in
prior steps.
21. After you have successfully completed all prior steps you can test the Compact Logix Ethernet port
by attempting to “ping” it. Open up a command prompt by clicking “start” then “run”, enter
“command” and then hitting “enter”. Once you see the window below type “ping” and hit enter.
You should see reply messages as shown below. If you don’t then the module is not responding. It
is important to note that you must give the PLC about 30 seconds to initialize the Ethernet port
before trying this.