Owner manual
Coverage size
TheHFLUM2-WRcoverageis360°
anditsreachrangesfrom3.3to26
feet(seenextpageforreach/sensitivity
adjustment).Actualcoveragemayvary
dependingonluminairecongurationand
environmentalconditions.
Lamp seasoning
Someorescentlampmanufacturers
recommendseasoningor“burningin”
lamps.Tomeetthisrecommendation,the
followingseasoningprocedureshouldbe
carriedoutfornewuorescentlamps.
• Connectluminaire,switchONforat
leastoneminute
• SwitchpowersupplyOFF/ONtwice
(mainorlightswitchwithin0.5–1sec)
• Alternatively,youcanstartthe
seasoningprocessbyusingthe
potentiometers.Turnall3setting
controlsfullyclockwise,thenturn
themiddlesettingcontrol(time)fully
counter-clockwiseandfullyclockwise
again(within10sec)
• Theseasoningprocessisconrmedby
switchingthelightOFFandbackON
againtwice
• ThelightisnowleftONforfourdays
withoutsensorfunction.Donot
disconnectthelightfromthemain
powersupplyduringthisperiod.
• Theluminaireautomaticallyreturnsto
sensormodeafter96hours
3.3 - 26 ft
1 - 8 m
3.3 - 13 ft
1 - 4 m
Setup & Commissioning
6
Test mode
• Ensurethatthesensorisintestmode.
- settimedelaytominimumsettingof
30seconds
- setlightleveltomaximum
(“day”setting,lightlevelfunction
overridden)
- setsensitivitytominimum
• TurnpowerONatthecircuitbreaker
(lightswillturnON).Afterawarmup
periodofuptooneminute,lightswill
turnOFFifthesensordoesnotdetect
motion.
• Walkinviewofsensor,lightsshouldturn
ON.Bestillfor30secondsandlights
shouldturnOFF.
Aftersetupandcommissioningtestsare
complete,adjustthelightlevel,timedelay,
andreachsettingstottheapplication
needs.