Datasheet

2
FPI 118FPI 018 FPO 118FPO 018
215
176
25
117
176
25
43
215
176
25
117
176
25
43
215
176
25
117
176
25
43
215
176
25
117
25
25
176
215
176
25
117
25
25
176
215
176
25
117
25
25
176
PRODUKTKATALOG - STEGO
FILTER MAT FM 086
Filter class 168 x 168 mm Average arrestance A
a
1 packing unit
G3 acc. to DIN EN 779 Art. No. 08635.0-00 84 % 5 pieces
AIRFLOW DIRECTION "OUT": INTAKE FILTER FPO 118
Art. No. Depth in enclosure Weight (approx.) Filter mat
11882.0-30 25 mm 0.4 kg G3 acc. to DIN EN 779, average arrestance A
a
84 %
AIRFLOW DIRECTION "OUT": FILTER FAN FPO 018
Art. No. Operating voltage Air volume,
free flow
Air volume
with exit filter
Current consumption
(50/60 Hz)
Power
consumption
Average noise level
(DIN EN ISO 4871)
Depth in
enclosure
Weight
(approx.)
Air outlet
01882.0-00 AC 230 V, 50/60 Hz 263 m³/h 137 m³/h 310/250 mA 45 W 56 dB 117 mm 1.6kg air-flaps
01882.9-00 AC 115 V, 50/60 Hz 313 m³/h 166 m³/h 560/470 mA 38 W 60 dB 117 mm 1.6kg air-flaps
warmcold
Filter Fan FPO 018
Intake Filter FPO 118
Air-flaps
Filter mat
SYSTEM FPO
TECHNICAL DRAWINGS
2
TECHNICAL DATASHEET
www.stego.de | www.stego.co.uk | www.stegonorden.se11.11.2015 | Specifications are subject to change without notice. Errors and omissions excepted. Suitability of this product for its intended use and any associated risks must be determined by the end customer/buyer in its final application.