User manual
14
741.011 | 12.18
EN
Set the functions (necessary for System 0.1, or as required for other systems. The functions can also
be set at a later date.)
19. Press SET to set the functions. F:01 (function number) flashes
(example in Fig. left).
or
Press to skip the setting of the functions; Ok flashes. Con-
tinue with step 28.
20. Press to select a different function; Function descriptions
in Section 11.3.
21. Press SET. oFF is displayed.
22. Press SET. oFF flashes.
23. Press . on flashes.
24. Press SET. The function is activated.
25. Set the characteristics (see Section 11.1, p. 26).
26. Press ESC.
27. Press . Ok flashes.
Finishing Initial commissioning
28. Press SET to finish the initial commissioning. The controller
switches to the operating mode Off (example in Fig. left).
or
Press /ESC to display the previous settings and correct them
if necessary.
Set the operating mode (off, manual, automatic)
29. Remove the front panel (Fig. left and Section 5.1.1).
30.
Notice
Danger of pump damage if run dry. Only switch the system to
manual or automatic mode when the system is filled.
Press and hold the mode button (arrow in Fig. left) for
2 seconds to change the operating mode; more information on
this is provided in Section 9.
31. Mount the front panel. The controller is now ready for opera-
tion.