User manual

Table Of Contents
1. Press SET. The Fix DOD level dialogue appears (Fig. left).
2. Press SET. The value flashes.
3.
Press D, Ñ to change the value.
4. Press SET. The value stops blinking.
U1 tolerance for timer
NOTICES
n Die charging time U1 counts down when the actual
battery voltage lies within the range of the upper charge
voltage U1 minus the tolerance threshold.
n This allows toleration of short charging interruptions that
only result in a small reduction of the charge voltage.
‘Main menu è Battery settings è NiCd battery settings
è U1 tolerance for timer
1. Press SET. The U1 tolerance for timer
dialogue appears
(Fig. left).
2. Press SET. The value flashes.
3.
Press D, Ñ to change the value.
4. Press SET. The value stops blinking.
Charging time U1
NOTICES
n Period for which the upper charge voltage U1 minus the
tolerance threshold is to be maintained.
n Countdown of the charging time U1 is reset when the
device is restarted and at the start of a new day.
n This also occurs when the upper charge voltage U1 minus
the tolerance threshold is not reached over a period
greater than 5 h (continuously).
n Countdown of the charging time U1 is also reset when the
specified discharge depth for DOD reset charging is
reached.
‘Main menu è Battery settings è NiCd battery settings
è Charging time U1’
1. Press SET. The Charging time U1 dialogue appears (Fig.
left).
2. Press SET. The value flashes.
3.
Press D, Ñ to change the value.
4. Press SET. The value stops blinking.
756.404 | Z01 | 16.06
82