User manual

Table Of Contents
switches to the Float charging mode. If the battery voltage cannot be maintained at
>2.53 V/cell for longer than 120 s during the the IA phase then the IA is ended and
the sequence starts again in the I phase. If the battery voltage reaches a value >=
2.6 V/cell during the IA phase then the MPPT 6000-M switches off the charging. The
device enters the OFF
state. This ends the IUIA charging cycle.
IUIA charge mode On/Off
‘Main menu è Battery settings è IUIA activation è On/Off ’
1. Press SET. The IUIA activation dialogue appears (Fig. left).
2.
Press D, Ñ to change the value.
3. Press SET. The value is adopted.
IUIA charge mode Cycle
‘Main menu è Battery settings è IUIA charge mode è Cycle ’
1. Press SET. The IUIA charge cycle dialogue appears (Fig.
left).
2.
Press D, Ñ to change the value.
3. Press SET. The value stops blinking.
8.5.10 Start boost charge
NOTICE!
Start boost charge
allows boost charging to be started manually.
The boost charging is executed using the previously configured parameters.
The device switches to float charging on completion of boost charging.
This function is only available for lead-acid and lead-gel/AGM battery types.
Once started, boost charging can only be stopped by switching the device off (OFF).
‘Main menu è Battery settings è Start boost charge’
1. Press SET. The Start boost charge dialogue appears. (Fig.
left).
2. Press SET for 1 s to start the boost charge.
756.404 | Z01 | 16.06