User manual
Table Of Contents
- 1 General information
- 2 Quick guide
- 3 Overview
- 4 Installation of the base system
- 5 Initial commissioning of the base system
- 6 Installation and initial commissioning of optional components
- 6.1 Commissioning the SD card (MPPT 6000-M only)
- 6.2 AUX 1,2,3 relay output connection (MPPT 6000-M only)
- 6.3 AUX IO remote control input connection (MPPT 6000-M only)
- 6.4 PA TS-S external temperature sensor connection
- 6.5 StecaLink slave connection
- 6.6 StecaLink master connection (MPPT 6000-M only)
- 6.7 UART/RS-232 interface connection (MPPT 6000-M only)
- 6.8 Redundancy function (MPPT 6000-S only)
- 6.9 Install cable strain relief
- 7 Display (layout, function, operation)
- 8 System functions
- 8.1 Protection functions
- 8.2 Battery type setting
- 8.3 Current limit system setting (MPPT 6000-M only)
- 8.4 Current limit device setting
- 8.5 Lead-acid battery system functions
- 8.5.1 Equalisation cycle mode
- 8.5.2 Battery control mode (MPPT 6000-M only)
- 8.5.3 Battery capacity test (MPPT 6000-M only)
- 8.5.4 Battery type
- 8.5.5 Battery capacity
- 8.5.6 Current limit system (MPPT 6000-M only)
- 8.5.7 Current limit device
- 8.5.8 Charge voltages
- 8.5.9 IUIA charge mode (MPPT 6000-M only)
- 8.5.10 Start boost charge
- 8.5.11 Battery temperature sensor
- 8.5.12 Cable compensation
- 8.5.13 PV string connection
- 8.5.14 Expert menu
- 8.6 Li-Ion battery system functions (MPPT 6000-M only)
- 8.7 NiCd battery system functions (MPPT 6000-M only)
- 8.8 StecaLink bus
- 8.9 Internal data logger
- 8.10 Clear log data
- 8.11 Clear event log
- 8.12 Factory settings
- 8.13 UART/RS-232 interface (MPPT 6000-M only)
- 8.14 Acoustic alarm
- 8.15 SD card (MPPT 6000-M only)
- 9 Control functions via AUX 1/2/3 (MPPT 6000-M only)
- 10 Troubleshooting
- 11 Maintenance, dismounting and disposal
- 12 Technical data
- 13 Guarantee conditions, exclusion of liability, contacts, notes

Tarom
MPP
T 6000-M
StecaLink
Slave Slave
StecaLink
Master
Tarom
MPP
T 6000-M
StecaLink
Slave Slave
StecaLink
Master
Fig. 15: Connection of two MPPT 6000-M devices via the master connection is not possible
The bus cable pin assignments are specified in the following table.
The StecaLink master connection of the MPPT 6000-M is galvanically isolated from the power unit.
StecaLink bus cable pin assignment: see
Ä
further information on page 47.
6.7 UART/RS-232 interface connection (MPPT 6000-M only)
NOTICE!
– The UART connection on the unit provides a serial interface with RS-232-compatible signal
levels. See
Ä
Chapter 12 ‘Technical data’ on page 124.
– The interface can be used for sending data from the device to a PC.
– Data transmission from a PC to the device is not possible.
– A 3-pin plug with screw terminals for constructing an individual cable is supplied with the
device.
– TxD, RxD and GND (signal ground) are present at the 3-pin connection, see printed label.
– The serial interface is galvanically isolated from the power unit connections.
– The interface can be switched on and off.
– The data output is fixed by the device and cannot be changed.
– Data is output at 1 minute intervals.
– For information on the data content of the serial output, see
Ä
Chapter 12.3 ‘UART/
RS-232 interface protocol (MPPT 6000-M only)’ on page 142.
– After activating the UART interface it can take up to one minute before the first data is
output.
1. Connect an external receiving device to the UART connection.
2.
For information on activating data output at the MPPT 6000-M, see
Ä
Chapter 8.13 ‘UART/
RS-232 interface (MPPT 6000-M only)’ on page 100.
Pin assignments:
Pin 1 (TX) 2 (RX) 3 (GND)
Signal TX RX Ground
756.404 | Z01 | 16.06