User manual
Table Of Contents
- 1 General information
- 2 Quick guide
- 3 Overview
- 4 Installation of the base system
- 5 Initial commissioning of the base system
- 6 Installation and initial commissioning of optional components
- 6.1 Commissioning the SD card (MPPT 6000-M only)
- 6.2 AUX 1,2,3 relay output connection (MPPT 6000-M only)
- 6.3 AUX IO remote control input connection (MPPT 6000-M only)
- 6.4 PA TS-S external temperature sensor connection
- 6.5 StecaLink slave connection
- 6.6 StecaLink master connection (MPPT 6000-M only)
- 6.7 UART/RS-232 interface connection (MPPT 6000-M only)
- 6.8 Redundancy function (MPPT 6000-S only)
- 6.9 Install cable strain relief
- 7 Display (layout, function, operation)
- 8 System functions
- 8.1 Protection functions
- 8.2 Battery type setting
- 8.3 Current limit system setting (MPPT 6000-M only)
- 8.4 Current limit device setting
- 8.5 Lead-acid battery system functions
- 8.5.1 Equalisation cycle mode
- 8.5.2 Battery control mode (MPPT 6000-M only)
- 8.5.3 Battery capacity test (MPPT 6000-M only)
- 8.5.4 Battery type
- 8.5.5 Battery capacity
- 8.5.6 Current limit system (MPPT 6000-M only)
- 8.5.7 Current limit device
- 8.5.8 Charge voltages
- 8.5.9 IUIA charge mode (MPPT 6000-M only)
- 8.5.10 Start boost charge
- 8.5.11 Battery temperature sensor
- 8.5.12 Cable compensation
- 8.5.13 PV string connection
- 8.5.14 Expert menu
- 8.6 Li-Ion battery system functions (MPPT 6000-M only)
- 8.7 NiCd battery system functions (MPPT 6000-M only)
- 8.8 StecaLink bus
- 8.9 Internal data logger
- 8.10 Clear log data
- 8.11 Clear event log
- 8.12 Factory settings
- 8.13 UART/RS-232 interface (MPPT 6000-M only)
- 8.14 Acoustic alarm
- 8.15 SD card (MPPT 6000-M only)
- 9 Control functions via AUX 1/2/3 (MPPT 6000-M only)
- 10 Troubleshooting
- 11 Maintenance, dismounting and disposal
- 12 Technical data
- 13 Guarantee conditions, exclusion of liability, contacts, notes

NOTICE!
– The charging function can be switched on or off by external devices via the AUX IO signal
input.
–
An external signal voltage of 5 VDC - 24 VDC at max. 3 mA or an external contact can be
connected. The external contact must be able to switch max. 15 VDC at 5 mA.
– Connect an external signal voltage between AUX IO (1) and (2). AUX IO (1) is the GND,
AUX IO (2) is the signal voltage input.
– Connect an external contact between AUX IO (2) and (3).
– A 3-pin plug with screw terminals for the external cable is supplied with the MPPT 6000-M.
AUX IO Description
1 (GND) GND reference for external signal voltage.
2 (Signal input) External signal voltage input connection.
3 (Signal output) Signal output for external switch.
1. Connect the external control source to the AUX IO signal input.
2. Configure the AUX IO function.
3. Configure the Device On/Off control.
Configuration of the AUX IO control function
NOTICE!
– The following properties can be assigned to the AUX IO connection:
– Ext. voltage on
Application of an external voltage at the AUX IO connection switches on charging by
the MPPT 6000-M.
– Ext. voltage off
Application of an external voltage at the AUX IO connection switches off charging by
the MPPT 6000-M.
– Ext. switch on
The closing of an external switch at the AUX IO connection switches on charging by
the MPPT 6000-M.
– Ext. switch off
The closing of an external switch at the AUX IO connection switches off charging by
the MPPT 6000-M.