User manual
Table Of Contents
- 1 General information
- 2 Quick guide
- 3 Overview
- 4 Installation of the base system
- 5 Initial commissioning of the base system
- 6 Installation and initial commissioning of optional components
- 6.1 Commissioning the SD card (MPPT 6000-M only)
- 6.2 AUX 1,2,3 relay output connection (MPPT 6000-M only)
- 6.3 AUX IO remote control input connection (MPPT 6000-M only)
- 6.4 PA TS-S external temperature sensor connection
- 6.5 StecaLink slave connection
- 6.6 StecaLink master connection (MPPT 6000-M only)
- 6.7 UART/RS-232 interface connection (MPPT 6000-M only)
- 6.8 Redundancy function (MPPT 6000-S only)
- 6.9 Install cable strain relief
- 7 Display (layout, function, operation)
- 8 System functions
- 8.1 Protection functions
- 8.2 Battery type setting
- 8.3 Current limit system setting (MPPT 6000-M only)
- 8.4 Current limit device setting
- 8.5 Lead-acid battery system functions
- 8.5.1 Equalisation cycle mode
- 8.5.2 Battery control mode (MPPT 6000-M only)
- 8.5.3 Battery capacity test (MPPT 6000-M only)
- 8.5.4 Battery type
- 8.5.5 Battery capacity
- 8.5.6 Current limit system (MPPT 6000-M only)
- 8.5.7 Current limit device
- 8.5.8 Charge voltages
- 8.5.9 IUIA charge mode (MPPT 6000-M only)
- 8.5.10 Start boost charge
- 8.5.11 Battery temperature sensor
- 8.5.12 Cable compensation
- 8.5.13 PV string connection
- 8.5.14 Expert menu
- 8.6 Li-Ion battery system functions (MPPT 6000-M only)
- 8.7 NiCd battery system functions (MPPT 6000-M only)
- 8.8 StecaLink bus
- 8.9 Internal data logger
- 8.10 Clear log data
- 8.11 Clear event log
- 8.12 Factory settings
- 8.13 UART/RS-232 interface (MPPT 6000-M only)
- 8.14 Acoustic alarm
- 8.15 SD card (MPPT 6000-M only)
- 9 Control functions via AUX 1/2/3 (MPPT 6000-M only)
- 10 Troubleshooting
- 11 Maintenance, dismounting and disposal
- 12 Technical data
- 13 Guarantee conditions, exclusion of liability, contacts, notes

6.2 AUX 1,2,3 relay output connection (MPPT 6000-M only)
CAUTION!
Danger of destruction of the relays. Observe the technical data of the relays, see
Ä
Chapter 12
‘Technical data’ on page 124. Only use AUX 1/2/3 for switching DC voltages of max. 60 VDC.
NOTICE!
– A 2-pin plug with screw terminals for the external cable is supplied with the MPPT 6000-M.
–
Each AUX connection has a separate COM and NO connection.
– The relay outputs are potential-free, normally-open contacts.
– The initial state of the contacts is normally-open.
– Multiple different events can be assigned to the AUX 1/2/3 outputs. Multiple events are
combined as logical "OR" values.
– The relay outputs can be used for switching devices or loads.
– Heavy loads connected directly to the battery can be switched using an additional power
relay connected to the AUX connection, e.g via the Steca PA EV 200.
1. Connect the external components to the AUX relay outputs.
2.
Configure the relay outputs as described in
Ä
Chapter 9 ‘Control functions via AUX 1/2/3
(MPPT 6000-M only)’ on page 103.
AUX 1 AUX 2 AUX 3 Description
1 (COM) 1 (COM) 1 (COM) Common relay contact
2 (NO) 2 (NO) 2 (NO) Normally open relay contact; the contact is open when the
relay is switched off.
6.3 AUX IO remote control input connection (MPPT 6000-M only)
CAUTION!
Risk of destroying the signal input. Observe the technical connection data, see
Ä
Chapter 12
‘Technical data’ on page 124.
756.404 | Z01 | 16.06