User manual
Table Of Contents
- 1 General information
- 2 Quick guide
- 3 Overview
- 4 Installation of the base system
- 5 Initial commissioning of the base system
- 6 Installation and initial commissioning of optional components
- 6.1 Commissioning the SD card (MPPT 6000-M only)
- 6.2 AUX 1,2,3 relay output connection (MPPT 6000-M only)
- 6.3 AUX IO remote control input connection (MPPT 6000-M only)
- 6.4 PA TS-S external temperature sensor connection
- 6.5 StecaLink slave connection
- 6.6 StecaLink master connection (MPPT 6000-M only)
- 6.7 UART/RS-232 interface connection (MPPT 6000-M only)
- 6.8 Redundancy function (MPPT 6000-S only)
- 6.9 Install cable strain relief
- 7 Display (layout, function, operation)
- 8 System functions
- 8.1 Protection functions
- 8.2 Battery type setting
- 8.3 Current limit system setting (MPPT 6000-M only)
- 8.4 Current limit device setting
- 8.5 Lead-acid battery system functions
- 8.5.1 Equalisation cycle mode
- 8.5.2 Battery control mode (MPPT 6000-M only)
- 8.5.3 Battery capacity test (MPPT 6000-M only)
- 8.5.4 Battery type
- 8.5.5 Battery capacity
- 8.5.6 Current limit system (MPPT 6000-M only)
- 8.5.7 Current limit device
- 8.5.8 Charge voltages
- 8.5.9 IUIA charge mode (MPPT 6000-M only)
- 8.5.10 Start boost charge
- 8.5.11 Battery temperature sensor
- 8.5.12 Cable compensation
- 8.5.13 PV string connection
- 8.5.14 Expert menu
- 8.6 Li-Ion battery system functions (MPPT 6000-M only)
- 8.7 NiCd battery system functions (MPPT 6000-M only)
- 8.8 StecaLink bus
- 8.9 Internal data logger
- 8.10 Clear log data
- 8.11 Clear event log
- 8.12 Factory settings
- 8.13 UART/RS-232 interface (MPPT 6000-M only)
- 8.14 Acoustic alarm
- 8.15 SD card (MPPT 6000-M only)
- 9 Control functions via AUX 1/2/3 (MPPT 6000-M only)
- 10 Troubleshooting
- 11 Maintenance, dismounting and disposal
- 12 Technical data
- 13 Guarantee conditions, exclusion of liability, contacts, notes

Switching on the cable compensation
The cable compensation corrects the deviation of the measured
battery voltage resulting from the voltage drop across the
battery cable.
NOTICES
n The unit is supplied with cable compensation switched off.
n The battery voltage sensor cable must be connected in
order to use cable compensation, see
Ä
Chapter 4.3.3
‘Connecting the battery voltage sensor’ on page 29.
n The voltage measured via the battery voltage sensor cable
is displayed in the measurements shown on the status
display of the device.
n Measuring the actual voltage at the battery allows the
device to compensate for voltage drops across the battery
cables. This can result in higher voltages at the battery
connection terminals on the controller.
n An Error event message is displayed if the battery voltage
sensor cable is not connected when the cable
compensation is switched on.
n If cable compensation is to be used in every member of a
master/slave system then this must be individually
installed and activated at each device.
1. Press ESC. The Battery settings menu appears.
2.
Press D, Ñ to select Cable compensation (Fig. left).
3. Press SET. The Cable compensation dialogue appears (Fig.
left).
4.
Press D, Ñ to select On.
5. Press SET. The line compensation is switched on.
756.404 | Z01 | 16.06