User manual
Table Of Contents
- 1 General information
- 2 Quick guide
- 3 Overview
- 4 Installation of the base system
- 5 Initial commissioning of the base system
- 6 Installation and initial commissioning of optional components
- 6.1 Commissioning the SD card (MPPT 6000-M only)
- 6.2 AUX 1,2,3 relay output connection (MPPT 6000-M only)
- 6.3 AUX IO remote control input connection (MPPT 6000-M only)
- 6.4 PA TS-S external temperature sensor connection
- 6.5 StecaLink slave connection
- 6.6 StecaLink master connection (MPPT 6000-M only)
- 6.7 UART/RS-232 interface connection (MPPT 6000-M only)
- 6.8 Redundancy function (MPPT 6000-S only)
- 6.9 Install cable strain relief
- 7 Display (layout, function, operation)
- 8 System functions
- 8.1 Protection functions
- 8.2 Battery type setting
- 8.3 Current limit system setting (MPPT 6000-M only)
- 8.4 Current limit device setting
- 8.5 Lead-acid battery system functions
- 8.5.1 Equalisation cycle mode
- 8.5.2 Battery control mode (MPPT 6000-M only)
- 8.5.3 Battery capacity test (MPPT 6000-M only)
- 8.5.4 Battery type
- 8.5.5 Battery capacity
- 8.5.6 Current limit system (MPPT 6000-M only)
- 8.5.7 Current limit device
- 8.5.8 Charge voltages
- 8.5.9 IUIA charge mode (MPPT 6000-M only)
- 8.5.10 Start boost charge
- 8.5.11 Battery temperature sensor
- 8.5.12 Cable compensation
- 8.5.13 PV string connection
- 8.5.14 Expert menu
- 8.6 Li-Ion battery system functions (MPPT 6000-M only)
- 8.7 NiCd battery system functions (MPPT 6000-M only)
- 8.8 StecaLink bus
- 8.9 Internal data logger
- 8.10 Clear log data
- 8.11 Clear event log
- 8.12 Factory settings
- 8.13 UART/RS-232 interface (MPPT 6000-M only)
- 8.14 Acoustic alarm
- 8.15 SD card (MPPT 6000-M only)
- 9 Control functions via AUX 1/2/3 (MPPT 6000-M only)
- 10 Troubleshooting
- 11 Maintenance, dismounting and disposal
- 12 Technical data
- 13 Guarantee conditions, exclusion of liability, contacts, notes

Configurable auxiliary contacts AUX 1–3 (MPPT 6000-M only)
Excess energy control hysteresis for battery
type: NiCd
Value range depends on the number of cells.
Setting as total battery voltage.
Factory setting 0.057 V/cell [0.4 VDC with number of cells = 7]
Setting range 0.1 VDC … 0.5 V/cell
Timer 1-4
Factory setting Day: none | Switch-off time 00:00 | Switch-on
time 00:00
Setting range Day: MON … SUN | Switch-on time 00:00 …
23:59 | Switch-off time 00:00 … 23:59
Evening light
Factory setting Switch-on delay 00:00 | Switch-on duration
00:01
Setting range Switch-on delay 00:00 … 12:00 | Switch-on
duration 00:00 … 16:00
Night light
Factory setting Switch-on delay 00:00 | Switch-off delay 00:00
Setting range Switch-on delay 00:00 … 12:00 | Switch-off
delay 00:00 … 16:00
Morning light
Factory setting Switch-on duration 00:01 | Switch-off duration
00:00
Setting range Switch-on duration 00:00 … 16:00 | Switch-off
delay 00:00 … 12:00
AUX IO (MPPT 6000-M only)
Plug 3-pin Phoenix Contact RM3.81, Type: MC 1.5/3-
ST-3.81; (fine strand) 0.14 mm
2
-1.5 mm
2
-
AWG 28 - 16
Permissible external signal voltage 5.0 VDC … 24 VDC
Current consumption from external signal
voltage
0.5 mA … 3.0 mA
Required external normally-open contact rating Min. 15.0 VDC; max. 5.0 mA
Mode AUX IO
Factory setting Ext. switch on
Setting range Ext. voltage on | Ext. voltage off | Ext. switch
on | Ext. switch off