User manual
Table Of Contents
- 1 General information
- 2 Quick guide
- 3 Overview
- 4 Installation of the base system
- 5 Initial commissioning of the base system
- 6 Installation and initial commissioning of optional components
- 6.1 Commissioning the SD card (MPPT 6000-M only)
- 6.2 AUX 1,2,3 relay output connection (MPPT 6000-M only)
- 6.3 AUX IO remote control input connection (MPPT 6000-M only)
- 6.4 PA TS-S external temperature sensor connection
- 6.5 StecaLink slave connection
- 6.6 StecaLink master connection (MPPT 6000-M only)
- 6.7 UART/RS-232 interface connection (MPPT 6000-M only)
- 6.8 Redundancy function (MPPT 6000-S only)
- 6.9 Install cable strain relief
- 7 Display (layout, function, operation)
- 8 System functions
- 8.1 Protection functions
- 8.2 Battery type setting
- 8.3 Current limit system setting (MPPT 6000-M only)
- 8.4 Current limit device setting
- 8.5 Lead-acid battery system functions
- 8.5.1 Equalisation cycle mode
- 8.5.2 Battery control mode (MPPT 6000-M only)
- 8.5.3 Battery capacity test (MPPT 6000-M only)
- 8.5.4 Battery type
- 8.5.5 Battery capacity
- 8.5.6 Current limit system (MPPT 6000-M only)
- 8.5.7 Current limit device
- 8.5.8 Charge voltages
- 8.5.9 IUIA charge mode (MPPT 6000-M only)
- 8.5.10 Start boost charge
- 8.5.11 Battery temperature sensor
- 8.5.12 Cable compensation
- 8.5.13 PV string connection
- 8.5.14 Expert menu
- 8.6 Li-Ion battery system functions (MPPT 6000-M only)
- 8.7 NiCd battery system functions (MPPT 6000-M only)
- 8.8 StecaLink bus
- 8.9 Internal data logger
- 8.10 Clear log data
- 8.11 Clear event log
- 8.12 Factory settings
- 8.13 UART/RS-232 interface (MPPT 6000-M only)
- 8.14 Acoustic alarm
- 8.15 SD card (MPPT 6000-M only)
- 9 Control functions via AUX 1/2/3 (MPPT 6000-M only)
- 10 Troubleshooting
- 11 Maintenance, dismounting and disposal
- 12 Technical data
- 13 Guarantee conditions, exclusion of liability, contacts, notes

NiCd battery settings (MPPT 6000-M only)
Temperature compensation for battery type:
NiCd
Factory setting On | Internal
Setting range On/Off | Internal/External
Cable compensation
Factory setting Off
Setting range On/Off
Configurable auxiliary contacts AUX 1–3 (MPPT 6000-M only)
Contact Normally open contact (NO), potential-free, 100
x 10
3
switching operations
Plug 2-pin Phoenix Contact RM3.81, Type: MC 1.5/2-
ST-3.81; (fine strand) 0.14 mm
2
-1.5 mm
2
-
AWG 28 - 16
Switchable voltage for resistive loads 30 VDC@1.0 A/60 VDC@0.3 A
Operating mode AUX 1…3
Factory setting Off
Setting range Off/On/Function
Deep-discharge protection disconnection
threshold for battery type:
Lead acid/Lead Gel/AGM
SOC | Voltage control
Factory setting 20 % | 11.4 VDC/22.8 VDC/34.2 VDC/45.6 VDC/
57.0 VDC
Setting range 10 % ... 70 % | 9.6 VDC … 12.6 VDC/19.2 VDC
… 25.2 VDC/28.8 VDC … 37.8 VDC/38.4 VDC …
50.4 VDC/48.0 VDC … 63.0 VDC
Reconnection hysteresis for battery type:
Lead acid/Lead Gel/AGM
SOC | Voltage control
Factory setting 20 % | 1.8 VDC/3.6 VDC/5.4 VDC/7.2 VDC/9.0
VDC
Setting range 5 % … 70 % | 0.2 VDC ... 3.0 VDC/0.5 VDC …
6.0 VDC/0.7 VDC … 9.0 VDC/1.0 VDC … 12.0
VDC/1.2 VDC … 15 VDC
Deep-discharge protection disconnection
threshold for battery type: Li-Ion
Value range depends on the number of cells.
Setting as total battery voltage.
Factory setting 3.2 V/ cell [22.4 VDC with number of cells = 7]
Setting range 0.5 V/cell… 6.0 V/cell