User manual

Table Of Contents
Lead acid/Lead Gel/AGM settings
Setting range 0 min ... 300 min
Equalisation cycle for battery type: Lead acid
Factory setting On | 30 days
Setting range On/Off | 1 … 185 days
Control mode for battery type:
Lead acid/Lead Gel/AGM
(MPPT 6000-M only, MPPT 6000-S permanently
set to voltage control)
Factory setting SOC
Setting range SOC/Voltage control
Temperature compensation for battery type:
Lead acid/Lead Gel/AGM
Factory setting On| Internal | -4.0 mV/cell/K/cell
Setting range On/Off | internal/external | -8.0 … 0.0 mV/cell/
K/cell
IUIA charge mode for battery type:
Lead acid/Lead Gel/AGM
(MPPT 6000-M only)
Factory setting Off | Cycle: 6 months
Setting range On/Off | Cycle: 1 … 6 months
Cable compensation
Factory setting Off
Setting range On/Off
Li-Ion battery settings (MPPT 6000-M only)
Number of cells
Factory setting 7 cells
Setting range 2 … 20 cells
Cell voltage
Factory setting 3.7 V/cell
Setting range 1.5 V/cell… 6.0 V/cell
Charge cut-off voltage
Factory setting 4.20 V/cell
Setting range 2.00 V/cell… 7.00 V/cell
Charge activation
756.404 | Z01 | 16.06
127