Event message
Cause Remedy
Type No. Text
Warning
79 PA HS400
communication
failed
The MPPT 6000-M can no
longer access one or
more previously
recognised PA HS400
devices. The connection
to the PA HS400 might
have been interrupted.
Check the StecaLink bus cables.
Check the address setting at the
PA HS400, restart the PA HS400
if necessary.
Check the StecaLink bus
termination and plug in a
termination plug if necessary.
Warning
79 79 MPPT slave
communication
failed
The MPPT 6000-M can no
longer access one or
more previously
recognised MPPT 6000-S
devices. The connection
might have been
interrupted.
Check the StecaLink bus cables.
Check the address setting at the
MPPT 6000-S, restart the MPPT
6000-S if necessary.
Check the StecaLink bus
termination and plug in a
termination plug if necessary.
Warning
79 79 Tarom 4545
communication
failed
The MPPT 6000-M can no
longer access one or
more previously
recognised Tarom 4545
devices. The connection
to the Tarom 4545 might
have been interrupted.
Check the StecaLink bus cables.
Check the address setting at the
Tarom 4545, restart the Tarom
4545 if necessary.
Check the StecaLink bus
termination and plug in a
termination plug if necessary.
Warning
84 Check voltage
settings
The automatically
detected system voltage
does not agree with the
manually set system
voltage.
Take the following measures:
1. Switch off the DC load circuit
breaker (solar module) and
secure it against being switched
on again. With 2 solar modules,
switch off both DC load circuit
breakers.
2. Determine the rated voltage of
the system.
3. Check the following points:
Is the manually set system
voltage the same as the actual
rated voltage of the system?
Correct if necessary!
Does the battery voltage lie
within the range of the rated
voltage of the system? If
necessary, charge the battery
with an external charger.
756.404 | Z01 | 16.06