User manual

Table Of Contents
Operation
‘Main menu è Settings AUX 1/2/3 è <Output> è Select function’
‘Main menu è Settings AUX 1/2/3 è <Output> è Function settings è Excess energy control’
U / SOC
0
1
t
1
2
‘Starting threshold’
‘Hysteresis’
9.3.6 Generator control
The generator control switches the output on as long as the battery has a low state of charge
1)
. The
generator control is suitable for a generator that is switched on when the battery is at a low state of
charge.
1)
Value in volts with voltage control and in percent with SOC control.
Switching behaviour
The output is switched on when the charge state falls below the starting threshold (Fig. below)
and is switched off when the charge state reaches the starting threshold plus the hysteresis value
.
Operation
‘Main menu è Settings AUX 1/2/3 è <Output> è Select function
‘Main menu è Settings AUX 1/2/3 è <Output> è Function settings è Excess energy control’
U / SOC
t
0
1
1
2
‘Starting threshold’
‘Hysteresis’
9.3.7 Timer 1 to 4
The timers can be used to switch the outputs on and off at specific times in a weekly cycle. The
switch-on and switch-off times for each weekday can be separately defined for each timer.
756.404 | Z01 | 16.06
109