Limit for charge voltage U1
NOTICES
n Maximum value of the upper charge voltage in a two-
stage charging process.
n Automatic adjustment of the upper charge voltage U1 due
to temperature compensation and prior depth of
discharge will be limited to this maximum value.
‘Main menu è Battery settings è NiCd battery settings
è Limit for charge volt. U1 U1’
1. Press SET. The Limit for charge volt. U1 dialogue
appears (Fig. left).
2. Press SET. The value flashes.
3.
Press D, Ñ to change the value.
4. Press SET. The value stops blinking.
Lower DOD limit
NOTICES
n Adjustment of the upper charge voltage U1 becomes
active when the battery drops below this depth of
discharge limit value (depth of discharge - DOD).
n A value of 0.05 means a 5 % depth of discharge relative to
the configured battery capacity.
‘Main menu è Battery settings è NiCd battery settings
è Lower DOD limit’
1. Press SET. The Lower DOD limit dialogue appears (Fig. left).
2. Press SET. The value flashes.
3.
Press D, Ñ to change the value.
4. Press SET. The value stops blinking.
U1 factor per DOD
NOTICES
n Factor per 1 % DOD, by which the upper charge voltage
U1 is adjusted.
n The value is specified in mV per cell.
‘Main menu è Battery settings è NiCd battery settings
è U1 factor per DOD
1. Press SET. The U1 factor per DOD dialogue appears (Fig.
left).
2. Press SET. The value flashes.
3.
Press D, Ñ to change the value.
4. Press SET. The value stops blinking.