User manual
Table Of Contents
- 1 General information
- 2 Quick guide
- 3 Overview
- 4 Installation of the base system
- 5 Initial commissioning of the base system
- 6 Installation and initial commissioning of optional components
- 6.1 Commissioning the SD card (MPPT 6000-M only)
- 6.2 AUX 1,2,3 relay output connection (MPPT 6000-M only)
- 6.3 AUX IO remote control input connection (MPPT 6000-M only)
- 6.4 PA TS-S external temperature sensor connection
- 6.5 StecaLink slave connection
- 6.6 StecaLink master connection (MPPT 6000-M only)
- 6.7 UART/RS-232 interface connection (MPPT 6000-M only)
- 6.8 Redundancy function (MPPT 6000-S only)
- 6.9 Install cable strain relief
- 7 Display (layout, function, operation)
- 8 System functions
- 8.1 Protection functions
- 8.2 Battery type setting
- 8.3 Current limit system setting (MPPT 6000-M only)
- 8.4 Current limit device setting
- 8.5 Lead-acid battery system functions
- 8.5.1 Equalisation cycle mode
- 8.5.2 Battery control mode (MPPT 6000-M only)
- 8.5.3 Battery capacity test (MPPT 6000-M only)
- 8.5.4 Battery type
- 8.5.5 Battery capacity
- 8.5.6 Current limit system (MPPT 6000-M only)
- 8.5.7 Current limit device
- 8.5.8 Charge voltages
- 8.5.9 IUIA charge mode (MPPT 6000-M only)
- 8.5.10 Start boost charge
- 8.5.11 Battery temperature sensor
- 8.5.12 Cable compensation
- 8.5.13 PV string connection
- 8.5.14 Expert menu
- 8.6 Li-Ion battery system functions (MPPT 6000-M only)
- 8.7 NiCd battery system functions (MPPT 6000-M only)
- 8.8 StecaLink bus
- 8.9 Internal data logger
- 8.10 Clear log data
- 8.11 Clear event log
- 8.12 Factory settings
- 8.13 UART/RS-232 interface (MPPT 6000-M only)
- 8.14 Acoustic alarm
- 8.15 SD card (MPPT 6000-M only)
- 9 Control functions via AUX 1/2/3 (MPPT 6000-M only)
- 10 Troubleshooting
- 11 Maintenance, dismounting and disposal
- 12 Technical data
- 13 Guarantee conditions, exclusion of liability, contacts, notes

Temperature compensation
NOTICE!
The temperature compensation offsets the charge cut-off voltage by the specified value per
battery cell (2 V cells in lead-acid batteries) and per degree Kelvin. For example, a temperature
coefficient of -4,0 mV/cell/K for a 48 V lead-acid battery causes the charge cut-off voltage to be
offset by -96 mV per degree Kelvin temperature difference relative to 25 °C.
✔
‘Main menu è Battery settings è Expert menu
è 17038 [SET] 1s è Temp. compensation
’
1. Press SET. The Temp. compensation dialogue appears (Fig.
left).
2.
Press D, Ñ to change the selection.
3. Select On/Off and press SET. The Temp. compensation
mode dialogue appears.
4.
Press D, Ñ to change the selection.
5. Press SET. The selection is adopted.
6. Press ESC to exit the selection dialogue.
7.
Press D, Ñ to change the selection.
8. Select Temperature coefficient and press SET. The
Temperature coefficient dialogue appears.
9. Press SET. The value flashes.
10.
Press D, Ñ to change the value.
11. Press SET. The value stops blinking and is adopted.
System voltage
✔
‘Main menu è Battery settings è Expert menu
è 17038 [SET] 1s è System voltage
’
1. Press SET. The System voltage dialogue appears (Fig. left).
2.
Press D, Ñ to change the selection.
3. Press SET. The selection is adopted.
NOTICE!
For lead-acid batteries, the system voltage always relates to the nominal voltage of the battery.
The device is configured for automatic voltage detection at the factory. This allows automatic
detection of the voltage levels 12 V, 24 V and 48 V. The system voltage must be directly
selected if the controller is to be used with system voltages of 36 V or 60 V. The system voltage
setting defines various other preset values and setting ranges.
756.404 | Z01 | 16.06
73