4.2 Installing the device
CAUTION!
Danger of damage to the inverter and reduction of power. Observe the following safety
requirements during installation:
The mounting location and immediate environment are permanently fixed, vertical, flat,
non-inflammable and not subject to constant vibration.
A free space of at least 60 mm must be present on all sides of the controller ( in Fig. 5).
The controller must be easily accessible and the display easily readable.
The controller is mounted as close as possible to the battery; the prescribed minimum
safety clearance of 0.5 m between the controller and battery is adhered to.
The controller must not be located
outdoors or in a location subject to rain or splashing water,
in dusty environments,
in stalls with active animal husbandry or
in direct sunlight.
The battery cable is no longer than 2 m (recommended), to keep cable losses and the
compensation voltage as low as possible.
Do not drill through the fastening openings / (Fig. 5).
1. Select the mounting location under consideration of the previously mentioned safety
requirements.
2. Position the controller level on the mounting surface and mark the mounting holes through
the fastening openings / shown in Fig. 5.
NOTICE!
The keyhole form of the two upper fastening holes makes it possible to first install the
screws for and then mark the holes to be drilled for with the device hung in place
(lower risk of incorrectly positioned drilled holes).
3. Remove the controller and drill the mounting holes.