User manual

Table Of Contents
Lead acid/Lead Gel/AGM settings
Float charge completion of charging voltage for
battery type: Lead acid/Lead Gel/AGM
Factory setting 14.1 VDC/28.2 VDC/42.3 VDC/56.4 VDC/70.5
VDC
Setting range 12.6 VDC ... 14.4 VDC/25.2 VDC ... 28.8 VDC/
37.8 VDC ... 43.2 VDC/50.4 VDC ... 57.6 VDC/
63.0 VDC ... 72.0 VDC
Boost charge switch-on threshold for battery
type: Lead acid/Lead Gel/AGM
SOC (MPPT 6000-M only) | Voltage control
Factory setting 70 % | 12.7 V/25.4 V/38.1 V/50.8 V/63.5 V
Setting range 40 % ... 70 % | 11.4 VDC ... 12.7 VDC/22.8
VDC ... 25.4 VDC/34.2 VDC ... 38.1 VDC/45.6
VDC ... 50.8 VDC/57.0 VDC ... 63.5 VDC
Boost charge completion of charging voltage
for battery type: Lead acid/Lead Gel/AGM
Factory setting 14.4 VDC/28.8 VDC/43.2 VDC/57.6 VDC/
72.0 VDC
Setting range 13.2 VDC ... 15.6 VDC/26.4 VDC ... 31.2 VDC/
39.6 VDC ... 46.8 VDC/52.8 VDC ... 62.4 VDC/
66.0 VDC ... 78.0 VDC
Boost charge duration for battery type: Lead
acid/Lead Gel/AGM
Factory setting 120 min
Setting range 0 min ... 300 min
Equalise charging switch-on threshold for
battery type: Lead acid/Lead Gel/AGM
SOC (MPPT 6000-M only) | Voltage control
Factory setting 40 % | 12.2 V/24.4 V/36.6 V/48.8 V/61.0 V
Setting range 10 % ... 60 % | 10.8 VDC ... 12.6 VDC/21.6
VDC ... 25.2 VDC/32.4 VDC ... 37.8 VDC/43.2
VDC ... 50.4 VDC/54.0 VDC ... 63.0 VDC
Equalise charging completion of charging
voltage for battery type: Lead acid
Factory setting 15.0 VDC/30.0 VDC/45.0 VDC/60.0 VDC/75.0
VDC
Setting range 13.8 VDC ... 15.9 VDC/27.6 VDC ... 31.8 VDC/
41.4 VDC ... 47.7 VDC/55.2 VDC ... 63.6 VDC/
69.0 VDC ... 79.5 VDC
Duration of equalise charging for battery type:
Lead acid
Factory setting 240 min
756.404 | Z01 | 16.06
126