User manual
Table Of Contents
- 1 General information
- 2 Quick guide
- 3 Overview
- 4 Installation of the base system
- 5 Initial commissioning of the base system
- 6 Installation and initial commissioning of optional components
- 6.1 Commissioning the SD card (MPPT 6000-M only)
- 6.2 AUX 1,2,3 relay output connection (MPPT 6000-M only)
- 6.3 AUX IO remote control input connection (MPPT 6000-M only)
- 6.4 PA TS-S external temperature sensor connection
- 6.5 StecaLink slave connection
- 6.6 StecaLink master connection (MPPT 6000-M only)
- 6.7 UART/RS-232 interface connection (MPPT 6000-M only)
- 6.8 Redundancy function (MPPT 6000-S only)
- 6.9 Install cable strain relief
- 7 Display (layout, function, operation)
- 8 System functions
- 8.1 Protection functions
- 8.2 Battery type setting
- 8.3 Current limit system setting (MPPT 6000-M only)
- 8.4 Current limit device setting
- 8.5 Lead-acid battery system functions
- 8.5.1 Equalisation cycle mode
- 8.5.2 Battery control mode (MPPT 6000-M only)
- 8.5.3 Battery capacity test (MPPT 6000-M only)
- 8.5.4 Battery type
- 8.5.5 Battery capacity
- 8.5.6 Current limit system (MPPT 6000-M only)
- 8.5.7 Current limit device
- 8.5.8 Charge voltages
- 8.5.9 IUIA charge mode (MPPT 6000-M only)
- 8.5.10 Start boost charge
- 8.5.11 Battery temperature sensor
- 8.5.12 Cable compensation
- 8.5.13 PV string connection
- 8.5.14 Expert menu
- 8.6 Li-Ion battery system functions (MPPT 6000-M only)
- 8.7 NiCd battery system functions (MPPT 6000-M only)
- 8.8 StecaLink bus
- 8.9 Internal data logger
- 8.10 Clear log data
- 8.11 Clear event log
- 8.12 Factory settings
- 8.13 UART/RS-232 interface (MPPT 6000-M only)
- 8.14 Acoustic alarm
- 8.15 SD card (MPPT 6000-M only)
- 9 Control functions via AUX 1/2/3 (MPPT 6000-M only)
- 10 Troubleshooting
- 11 Maintenance, dismounting and disposal
- 12 Technical data
- 13 Guarantee conditions, exclusion of liability, contacts, notes

Event message
Cause Remedy
Type No. Text
Warning
55 Bat. sense
open
The line compensation
has been manually
switched on but the
controller has not
detected a battery
voltage.
Check the following points:
n Battery voltage sensor cable
correctly connected?
n Open-circuit in sensor cable?
n Sensor cable fuse/breaker
blown/triggered?
Warning
56 Bat. sense
wrong
polarity
The battery voltage
sensor cable has been
connected with the
incorrect polarity.
Connect the battery voltage
sensor cable with the correct
polarity.
Warning
57 Ext. Bat.
sense short
A short-circuit exists in
the battery voltage
sensor cable.
Check the following points:
n Battery voltage sensor cable
correctly connected?
n Short-circuit in sensor cable?
Warning
58 PV 1
wrong
polarity
The module at
connection M1 is
connected with the
wrong polarity.
Take the following measures:
1. Switch off the DC load circuit
breaker (solar module) and
secure it against being switched
on again. With 2 solar modules,
switch off both DC load circuit
breakers.
2. Disconnect module 1.
3. Check the polarity.
4. Connect module 1 with the
correct polarity.
Warning
59 PV 2
wrong
polarity
The module at
connection M2 is
connected with the
wrong polarity.
Take the following measures:
1. Switch off the DC load circuit
breaker (solar module) and
secure it against being switched
on again. With 2 solar modules,
switch off both DC load circuit
breakers.
2. Disconnect module 2.
3. Check the polarity.
4. Connect module 2 with the
correct polarity.
Error
70 PV 1 voltage
too high
The module voltage at
connection M1 (solar
module 1) is too high.
Check the installation and
design.
Error
71 PV 2 voltage
too high
The module voltage at
connection M2 (solar
module 2) is too high.
Check the installation and
design.