8 Fault diagnosis and troubleshooting
Fault diagnosis and troubleshooting of the individual inverter is described in the
Steca Solarix PI operating instructions.
Fault Cause Remedy
LED on slave does not
light up
Data cable not
inserted properly
Data cable de-
fective
• Slave defective
Attention
Danger of damage to the
inverter.
Disconnect the battery and
the power cable from the
slave before working on the
data cable. Then reconnect
battery cable.
Connect the power cable only
after completion of all work.
Ensure that the data cable is
inserted properly.
If LED does not light up,
replace the data cable.
If LED does not light up,
replace the slave.
LED on master does not
light up
• Master defective
Replace master,
e.g. rewire system with a
previous slave as master
The system does not
work, although the
master and slave(s) are
in working order
• Parallel switch
box defective
Replace parallel switch box
LEDs on inverters signal
a malfunction
• Wiring fault
Check the wiring
The green Info LED on
the PA Link1 is not il-
luminated
No data connec-
tion to Solarix PI
Check RJ45 wiring between
PA Link1 and Solarix PI