User manual

Technical data
operating voltage: : 230 V AC +7/-5%
frequency: : 50 bis 60 Hz
power input: : max. 10 A
source 1 source 2
output voltage: : 0,005 .... 40 V 0,005 .... 40 V
output current:
: 0,003 ....10,0 A 0,003 ....10,0 A
voltage stability with +7/ -5% mains fluctuation: : < 1 mV < 1 mV
load compensating with 100% load change: : 3 mV 3 mV
current stability with +6 / -10 % mains fluctuation: : 1 mA 1 mA
remaining ripple with nominal load: : ca. 2mV
eff
bzw. 4 mA
ef
f
ca. 2mV
eff
bzw. 4 mA
ef
f
mains fuse: : 2x 4,0A T 2x 4,0A T
acting voltage display: : LCD with 3½ digits LCD with 3½ digits
current display: LCD with 3½ digits LCD with 3½ digits
weight: : ca. 23 kg
dimensions (B x H x T): : 451 x 134 x 410 mm
site conditions
operating temperature area: : +10 °C bis +35 °C
Air humidity: : max. 85 %
air pressure: : 800 bis 1333 hPa
Statron Gerätetechnik GmbH
Ehrenfried-Jopp-Straße 59
15517 Fürstenwalde
Tel.: (03361) 37 21 01
Fax: (03361) 37 21 03
e-Mail : statron@statron.de
Internet: www.statron.de

Summary of content (4 pages)