Instruction Manual COMMERCIAL GAS WATER HEATERS POWER VENT/POWER DIRECT VENT GAS MODELS WITH HOT SURFACE IGNITION MODELS SHE50 100 SERIES 124/125 Ashland City, TN 37015 www.statewaterheaters.com • For Your Safety • AN ODORANT IS ADDED TO THE GAS USED BY THIS WATER HEATER. Thank you for buying this energy efficient water heater. We appreciate your confidence in our products. ALL TECHNICAL AND WARRANTY QUESTIONS: SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS PURCHASED.
Table of contents Safe installation, use and service.................................3 Massachusetts......................................................................22 APPROVALS..................................................................................3 Commonwealth of Massachusetts............................................22 General safety information..............................................4 Installation of Carbon Monoxide Detectors...............................
Safe installation, use and service The proper installation, use and servicing of this water heater is extremely important to your safety and the safety of others. Many safety-related messages and instructions have been provided in this manual and on your own water heater to warn you and others of a potential injury hazard. Read and obey all safety messages and instructions throughout this manual.
General safety information Precautions Hydrogen Gas Flammable DO NOT USE THIS APPLIANCE IF ANY PART HAS BEEN UNDER WATER. Immediately call a qualified service agency to inspect the appliance and to make a determination on what steps should be taken next. Explosion Hazard If the unit is exposed to the following, do not operate heater until all corrective steps have been made by a qualified service agency. Flammable hydrogen gases may be present. 1. External fire.
General safety information 5
General Safety Information Fire or Explosion Hazard Fire Hazard Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. For continued protection against risk of fire: Avoid all ignition sources if you smell gas. Do not expose water heater controls to excessive gas pressure. Do not install water heater on carpeted floor. Do not operate water heater if flood damaged. Use only the gas shown on the water heater rating plate.
Introduction Detailed installation diagrams are also found in this manual. These diagrams will serve to provide the installer with a reference. It is essential that all venting, water piping, gas piping and wiring be installed as shown. Thank You for purchasing this water heater. Properly installed and maintained, it should give you years of trouble free service.
Features and components Get to Know Your Water Heater - Gas Models A Control Assembly B Blocked Inlet Switch C Blocked Outlet Switch D Fan Prover Switch E Blower Assembly F Burner Assembly G Flame Sensor H Hot Surface Igniter I Junction Box J Gas Valve Assembly K Display Board L Top Plastic Enclosure M Display Enclosure ** N Exhaust Elbow Assembly ** O Condensate Tubing P Off/On Switch Q Display Label R Hot Water Outlet T Gas Supply U Main Manual Gas Shutoff Val
Installation consideration Rough In Dimensions FIGURE 1A. Table 1 – Rough-In-Dimensions Units A B C D E F G H I Inches 66.75 49.25 22.00 15.75 3.00 8.00 8.00 62.00 65.00 cm 169.5 125.09 55.88 40.00 7.62 20.32 20.32 157.48 165.1 Top/Side Inlet and Outlet: 3/4” NPT Gas Inlet: 1/2” NPT Table 2 – Capacity, Gas and Electrical Characteristics Approximate Capacity Manifold Pressure Electrical Characteristics U.S. Gals. Liters Gas Type “WC kPA Volts/Hz Amperes 50 189 Nat.
Locating the Water Heater Carefully choose a location for the new water heater. The placement is a very important consideration for the safety of the occupants in the building and for the most economical use of the appliance. CAUTION Property Damage Hazard • All water heaters eventually leak. • Do not install without adequate drainage. Whether replacing an existing water heater or installing the water heater in a new location obser ve the following critical points: 1.
is installed in an alcove or closet, the entire floor must be covered by the panel. Failure to heed this warning may result in a fire hazard. • Do not apply insulation to the top of the water heater, as this will interfere with safe operation of the blower assembly. • Do not cover the outer door, thermostat or temperature & pressure relief valve. • Do not cover the instruction manual. Keep it on the side of the water heater or nearby for future reference.
Outdoor Air Through Two Openings ventilation systems, clothes dryers and fireplaces shall also be considered in determining the adequacy of a space to provide combustion, ventilation and dilution air. Unusually Tight Construction In unconfined spaces in buildings, infiltration may be adequate to provide air for combustion, ventilation and dilution of flue gases. However, in buildings of unusually tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.
Air From Other Indoor Spaces 1. 1 square inch per 3000 Btu/hr (733 mm2 per kW) of the total input rating of all appliances located in the enclosure, and 2. Not less than the sum of the areas of all vent connectors in the space. Outdoor Air Through Two Horizontal Ducts FIGURE 7. FIGURE 6. The confined space shall be provided with two permanent openings, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. See Figure 7.
Installing the new water heater Chemical Vapor Corrosion CORROSION OF THE FLUEWAYS AND VENT SYSTEM MAY OCCUR IF AIR FOR COMBUSTION CONTAINS CERTAIN CHEMICAL VAPORS. SUCH CORROSION MAY RESULT IN FAILURE AND RISK OF ASPHYXIATION. Spray can propellants, cleaning solvents, refrigerator and air conditioning refrigerants, swimming pool chemicals, calcium and sodium chloride (water softener salt), waxes, and process chemicals are typical compounds which are potentially corrosive.
Mixing Valves Dishwashing Machines Water temperature over 125°F (52°C) can cause severe burns instantly resulting in severe injury or death. Children, the elderly and the physically or mentally disabled are at highest risk for scald injury. Feel water before bathing or showering. All dishwashing machines meeting the National Sanitation Foundation requirements are designed to operate with water flow pressures between 15 and 25 pounds per square inch (103 kPa and 173 kPa).
• The hot water line from the water heater should be vertical past any mixing valve or supply line to the heating system to remove air bubbles from the system. • Do not connect the water heater to any system or components previously used with non-potable water heating appliances when used to supply potable water. • These water heaters cannot be used in space heating applications only. Figure 10.
No valve or other obstruction is to be placed between the Temperature-Pressure Relief Valve and the tank. Do not connect discharge piping directly to the drain unless a 6” (15.2 cm) air gap is provided. To prevent bodily injury, hazard to life, or property damage, the relief valve must be allowed to discharge water in adequate quantities should circumstances demand. If the discharge pipe is not connected to a drain or other suitable means, the water flow may cause property damage.
Gas Piping Gas Supply Systems Make sure gas supplied is same type listed on model rating plate. The inlet gas pressure must not exceed 14 inch water column (3.5 kPa) for natural and propane gas (L.P.). The minimum inlet gas pressure shown on rating plate is that which will permit firing at rated input. Low pressure building gas supply systems are defined as those systems that cannot under any circumstances exceed 14” W.C. (1/2 PSI Gauge). These systems do not require pressure regulation.
54) or the Natural Gas and Propane Installation Code (CAN/CSA B149.1) whichever applies. Copper or brass tubing and fittings (except tin lined copper tubing) shall not be used. CONDENSATE BUILD-UP WILL BLOCK THE EXHAUST OUTLET, WHICH WILL CAUSE IMPROPER OPERATION. If the gas control valve is subjected to pressures exceeding 1/2 psi (3.5 kPa), the damage to the gas control valve could result in a fire or explosion from leaking gas.
Filling the Water Heater technical support phone number listed on the water heater label for more information. VENT PIPE TERMINATION The first step is to determine where the vent pipe will terminate. See Figures 16, 17, and 18. The vent may terminate through a sidewall as shown in Figures 16 and 17 or through the roof as shown in Figures 18 and 19.
U.S. INSTALLATIONS: of sagging or other stresses in joints as a result of misalignment of any components in the system. If any of these conditions are found, they must be corrected in accordance with the venting instructions in this manual before completing installation and putting the water heater into service. NOTE: This unit can be vented with PVC pipe materials (DWV ASTM-D2665 or CSA B181.2; Schedule 40, 80, 120 ASTM-D1785 or CSA B137.3; or SDR Series ASTM-D2241 or CSA B137.
Installation Requirements - Commonwealth of Massachusetts Commonwealth of Massachusetts observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a) 1 through 4.
Termination Clearances Sidewall Power Vent POWER VENT (using room air for combustion) EXTERIOR CLEARANCES FOR SIDEWALL VENT TERMINATION G V D H A v E L v B FI XE D CLOSED V F OPERABLE V OPERABLE V B B C B B FI XE D CLOSED V M X V K J A X V B V X VENT TERMINAL AIR SUPPLY INLET AREA WHERE TERMINAL IS NOT PERMITTED Figure 13 Vent terminal clearances for “Power Vent” installations. Power Vent configurations use room air for combustion.
Termination Clearances Sidewall Direct Vent DIRECT VENT (using outdoor air for combustion) EXTERIOR CLEARANCES FOR SIDEWALL VENT TERMINATION G V D H A v E L v B FI XE D CLOSED V F B B C OPERABLE V OPERABLE V B B FI XE D CLOSED V M X V K J A X V B V VENT TERMINAL X AIR SUPPLY INLET AREA WHERE TERMINAL IS NOT PERMITTED Figure 14 Vent terminal clearances for “Direct Vent” installations. Direct Vent configurations use outdoor air for combustion.
SEQUENCE OF INSTALLATIONS, FIGUREs 15 – 16B Installation Sequence Cut a length of PVC pipe about 3.5 inches (8.9 cm) longer than the wall thickness at the opening. Glue the vent terminal to this section of pipe. Slide the wall plate over the pipe to stop against the vent terminal. Place a bead of caulking (not supplied) around the gap between the pipe and cover plate. Apply enough to fill some of the gap between the pipe and wall.
VERTICAL VENT TERMINAL INSTALLATION WHEN TERMINATING THROUGH A ROOF, THE FOLLOWING SPECIFICATIONS PERTAINING TO TERMINAL LOCATION MUST BE FOLLOWED. 1. Proper support must be provided for all pipe protruding through the roof. 2. The vertical roof terminations should be sealed with a plumbing roof boot or equivalent flashing. 3. The intake vent termination and the exhaust vent termination must penetrate the same side of roof. 4.
Concentric vent installation 1. Determine best location for termination kit. This appliance is certified for concentric venting with concentric vent kit #9003910105 and #9006328005. Follow instructions below for proper installations. NOTE: Roof termination is preferred since it is less susceptible to damage, has reduced chances to intake contaminants, and less visible vent vapors. TABLE 6 – KIT COMPONENTS 2. Cut 1 hole (5 in. diameter) Each kit is comprised of the following: 3.
5. Secure assembly to roof structure as shown in Figure 24 using field supplied metal strapping or equivalent support material. NOTE: Ensure termination height is above the roof surface or anticipated snow level as shown in Figure 24. 6. Inst all rain c ap and small diameter pipe assembly in r o o f p e n e t r a t i o n a s s e m b l y, E n s u r e s m a l l d i a m e t e r pipe is cemented and bottomed in Y concentric fitting. 7.
MULTI-CONCENTRIC VENT TERMINATIONS 5. Install rain cap and small diameter pipe assembly in Y concentric fitting and large pipe assembly. Ensure small diameter pipe is bottomed and cemented in Y concentric fitting. When two or more appliances are direct vented with concentric vent terminations near each other, each appliance must be individually vented. NEVER common vent this appliance.
Direct vent diagram 12” MINIMUM CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL 12” MINIMUM CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL Figure 30. Figure 29. 24” MINIMUM SEPARATION. EXHAUST MUST BE AT SAME LEVEL OR ABOVE INTAKE TERMINAL. Figure 31. Figure 32. When direct venting through the wall, as shown in Figure 33, the exhaust should terminate a minimum of 24” from the air intake. The exhaust may be rotated up to 45 degrees left or right as long as the 24” distance is maintained.
Vent Pipe Preparation PRIMER 1. INITIAL PREPARATION. It is recommended that Tetrahydrofuran (THF) be used to prepare the surfaces of pipe and fittings for solvent welding. Do not use water, rags, gasoline or any other substitutes for cleaning PVC or CPVC surfaces. A chemical cleaner such as MEK may be used. A.) Make sure the solvent cement you are planning to use is designed for the specific application you are attempting. B.
B. Deburring Use a knife, plastic pipe deburring tool, or file to remove burrs from the end of small diameter pipe. Be sure to remove all burrs from around the inside as well as the outside of the pipe. A slight chamfer (bevel) of about 10°-15° should be added to the end to permit easier insertion of the pipe into the end of the fitting. Failure to chamfer the edge of the pipe may remove cement from the fitting socket, causing the joint to leak. STEP B C.
Controls and Switches pressure to change the electrical contacts from normally closed to open. When this switch prevents the unit from igniting, most likely the exhaust is blocked by some means. Check to see if the condensate is allowed to flow freely from the exhaust elbow and for obstructions in the exhaust venting and exhaust vent terminal. Also verify that the vent length does not exceed the maximum allowed as shown in the Vent Section of this manual.
CAUTION LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION. VERIFY PROPER OPERATION AFTER SERVICING. THIS WATER HEATER IS POLARITY SENSITVE. B EFO R E A PPLYI N G ELECTRICITY TO THIS HEATER BE CERTAIN THAT SUPPLY NEUTRAL WIRE TO GROUND CHECK INDICATES ZERO VOLTAGE. Power Vent Wiring Schematic - Figure 35.
FOR YOUR SAFETY READ BEFORE LIGHTING WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life. BEFORE OPERATING: ENTIRE SYSTEM MUST BE FILLED WITH WATER AND AIR PURGED FROM ALL LINES. A. This appliance does not have a pilot. It is equipped with an ignition device which automatically lights the burner. Do NOT try to light the burner by hand. B. BEFORE OPERATING smell all around the appliance area for gas.
Temperature regulation It is recommended that lower water temperatures be used to avoid the risk of scalding. It is further recommended, in all cases, that the water temperatures be set for the lowest temperature which satisfies your hot water needs. This will also provide the most energy efficient operation of the water heater. Valves for reducing the point-of-use temperature by mixing cold and hot water are available, see Figure 8.
Control system operation Overview User Input Buttons The water heaters covered in this manual are equipped with an electronic control system that regulates water temperature inside the storage tank. Heating cycles and ignition are managed by the control system. The ECO (energy cut out), Flame Sensor, pressure switches and Temperature Probe is monitored by the control system. The Combustion Blower, Igniter and the 24 Volt Gas Valve are all energized by the control system.
Status Icons The Status Icons are displayed on the Desktop screen and convey operational and diagnostic information. The icons are described in the table below. Table 9 Icon Description Water temperature in the tank has fallen. Shaded area of the animated thermometer icon will rise and fall in response to water temperature in the storage tank as sensed from the Temperature Probe. Water temperature in the tank has reached the Operating Set Point. The control system enters the Standby mode.
Operating States The current operational state of the water heater is displayed on the Desktop screen as the "Status." The common operational states are described in the table below. Table 10 State Description Standby The water heater is not in an active heating cycle. IE: the Tank Temperature is at or above the Operating Set Point. Input Verification The control system is conducting a diagnostic check at the beginning of a heating cycle.
User Settings & Control System Menus Temperatures Operating Set Point And Differential Adjustment The Operating Set Point is adjustable from 90°F (42°C) to 180°F (82°C) for commercial and 160°F (71°C) on residential models. The factory setting is 120°F (49°C). The Differential is adjustable from 2° to 20°. The factory setting is 8°. These user settings are accessed from the Temperatures menu. These instructions explain how to adjust these settings and navigate the control system.
Temperatures (cont) Description/Action Display • Tank Temperature - non adjustable - control system sensed temperature from the Temperature Probe. • Tank Probe Offset - adjustable user setting, range -5° to +5° (factory setting 0°). The Tank Probe Offset is used to calibrate control system temperature sensing. This can improve the precision of temperature control in the storage tank and at points of use.
Display Settings Description/Action Display Select Display Settings from the Main Menu and press the Operational Button under "SELECT" to enter this menu. This menu contains adjustable display options for viewing information on the LCD screen. Use the Up & Down Buttons to navigate the menu. Display Settings • Temperature Units - Adjustable user setting that changes temperature units display to Celsius °C or Fahrenheit °F.
Current Fault Description/Action Display Select Current Fault from the Main Menu and press the Operational Button under "SELECT" to enter this menu. This menu contains non adjustable operational information. Use the Up & Down Buttons to navigate the menu. Blocked Exhaust Fault occurred 2 mins ago The exhaust is blocked or restricted. Ensure condensate hose is draining. This menu contains the current Fault or Alert error message. The time the Fault or Alert message occurred appears directly below.
Service Contact Information The control system has a discrete menu that Installing contractors and/or service agents can access to enter contact information for their customers. This contact information will be displayed with all Fault and Alert messages. Description/Action Display From the Desktop Screen press and hold down the middle (unmarked) Operational Button for 30 seconds and then release it.
For your information Start Up Conditions a. A concentration of sulfate in the supply water. b. Little or no dissolved oxygen in the water. SMOKE/ODOR c. A sulfate reducing bacteria which has accumulated within the water heater (this harmless bacteria is nontoxic to humans). It is not uncommon to experience a small amount of smoke and odor during the initial start-up. This is due to burning off of oil from metal parts, and will disappear in a short while. d. An excess of active hydrogen in the tank.
Periodic maintenance Venting System Inspection conductivity and should be checked and/or replaced more often than an anode rod that appears to be intact. Replacement of a depleted anode rod can extend the life of your water heater. Inspection should be conducted by a qualified technician, and at a minimum should be checked annually after the warranty period. Artificially softened water is exceedingly corrosive because the process substitutes sodium ions for magnesium and calcium ions.
2. Ensure the cold water inlet valve is open. Burn harzard. 3. Open a nearby hot water faucet and let the water run until the water is no longer hot. Then close the hot water faucet. Hot water discharge. 4. Connect a hose to the drain valve and terminate it to an adequate drain. Keep hands clear of drain valve discharge. 5. Ensure the drain hose is secured before and during the entire flushing procedure. Flushing is performed with system water pressure applied to the water heater. 6.
Maintenance Temperature-Pressure Relief Valve Test If the Temperature-Pressure Relief Valve on the water heater weeps or discharges periodically, this may be due to thermal expansion. Burn hazard. Note: Excessive water pressure is the most common cause of Temperature-Pressure Relief Valve leakage. Excessive water system pressure is most often caused by “thermal expansion” in a “closed system.” See Closed Water Systems and Thermal Expansion on pages 15 and 16.
Leakage checkpoints Never use this water heater unless it is completely filled with water. To prevent damage to the tank, the tank must be filled with water. Water must flow from the hot water faucet before turning “ON” gas to the water heater. A *Condensation may be seen on pipes in humid weather or pipe connections may be leaking. B. *The anode rod fitting may be leaking. C. Small amounts of water from temperature-pressure relief valve may be due to thermal expansion or high water pressure in your area.
Troubleshooting Installation Checklist Flow Chart. The list below represents some of the most critical installation requirements that, when overlooked, often result in operational problems, down time and needless parts replacement. This is not a complete list. Before performing any troubleshooting procedures use the list below to check for installation errors. Costs to correct installation errors are not covered under the limited warranty.
Sequence Of Operation Flow Chart If tank temperature drops below Operating Set Point minus Differential setting a heating cycle is activated Control System performs diagnostic checks Normal State of all pressure switches and ECO are checked Blower Prover pressure switch verified open All other pressure switches and ECO are verified closed NO Control System Locks Out Displays Fault Msg Combustion Blower is energized Pre-Purge cycle Blower Prover switch contacts confirmed closed by control system NO Co
Operational Problems If the Main Burner ignites momentarily but does not sustain ignition allow the water heater to try to ignite up to two more times until control system locks out and the Ignition Failure Fault message is displayed on the control system's LCD. If the water heater is experiencing rough starts - see Rough Starting, Rough Operation on this page.
Note: If you are not qualified and licensed or certified as required by the authority having jurisdiction to perform a given task do not attempt to perform any of the diagnostic or service procedures described in the following section. mark. The water heater will continue to operate during an Alert condition but the water heater must be serviced by a qualified service agent as soon as possible.
Fault And Alert Messages Call the technical support phone number listed on the back cover for further technical assistance or to locate a qualified service agent in your area. Possible Causes - Check/Repair Displayed Fault/Alert Message • The water heater’s control system is polarity sensitive and will lock out and disable heating operation if the polarity of the power supply is reversed. The control system will display the “AC Reversed” Fault message on the LCD in this condition.
Fault And Alert Messages (cont) Call the technical support phone number listed on the back cover for further technical assistance or to locate a qualified service agent in your area. Possible Causes - Check/Repair Displayed Fault/Alert Message • The control system has detected the Blower Prover Switch contacts are closed when they should be open at the beginning of a heating cycle. • Pinched/shorted Blower Prover Switch wiring. • Jumper wire connected to the Blower Prover Switch - remove jumper wire.
Notes 56
Notes 57
Notes 58
Limited Warranty State Water Heaters, the warrantor, extends the following LIMITED WARRANTY to the owner of this water heater. 1.
www.statewaterheaters.com 500 Tennessee Waltz Parkway, Ashland City, TN 37015 Tech Support: 800-527-1953 Parts: 800-433-2545 Copyright © 2012 State Water Heaters, All rights reserved.