- Instruction Manual Residential Gas Water Heater

20
INSTALLATION OF VENT SYSTEM
Beforebeginninginstallationofpipingsystemthoroughlyread
the section of this manual VENT PIPE PREPARATION.
If you are installing your system so that it vents through roof,
please refer to section titled INSTALLATION OF VERTICAL
VENT SYSTEM.
VENT TERMINAL INSTALLATION, SIDEWALL
1. Installtheventterminalbyusingthecoverplateasatemplate
tomarktheholefortheventpipetopassthroughthewall.
BEWARE OF CONCEALED WIRING AND PIPING INSIDE
THE WALL.
2. If the Vent Terminal is being installed on the outside of a
finishedwall, itmaybeeasier tomark boththeinsideand
outsidewall.Aligntheholesbydrillingaholethroughthe
centerofthetemplatefromtheinsidethroughtotheoutside.
Thetemplatecannowbepositionedontheoutsidewallusing
thedrilledholeasacenteringpointforthetemplate.
3. A)MASONRYSIDEWALLS
Chiselanopeningapproximatelyonehalfinch(1.3cm)larger
thanthemarkedcircle.
B)WOODENSIDEWALLS
Drillapilotholeapproximatelyonequarterinch(0.64cm)outside
ofthemarkedcircle.Thispilotholeisusedasastartingpoint
for a saws-all or sabre saw blade. Cut around the marked
circlestayingapproximatelyonequarterinch(0.64cm)outside
ofthe line. (This will allowthe ventto easilyslide through
the opening. The resulting gap will be covered up by the
VentTerminalcoverplate.)Repeatthissteponinsidewallif
necessary.
SEQUENCE OF INSTALLATIONS, FIGURE 18A
CutalengthofPVCpipeabout3.5inches(8.9cm)longerthanthe
wall thickness at the opening. Glue the vent terminal to this
sectionofpipe.Slidethewallplateoverthepipetostopagainst
theventterminal.Placeabeadofcaulking(notsupplied)around
thegap between the pipe andcover plate.Apply enough to
fillsomeofthegapbetweenthepipeandwall.Placesomeof
thecaulkingonthebackoftheplatetoholditagainstthewall
afterinstallation.Iftheventpipeisinstalleduptothewall,with
acouplingontheendagainstthewallopening,thepipewith
thevent terminal can be prepared for gluingbefore inserting
through the wall. Slide the pipe through the wall and insert
intothecouplingontheothersideofthewall,makingsurethat
theventterminal endsup pointedin the correctposition,see
Figure18A.
VENT TERMINATION - FIGURE 18A.
DIRECT VENTING
Theairintakeprovidedontheunitcontainsameshscreentoprevent
largeparticlesfromenteringtheunit.
FIGURE 18B.
WHEN THE UNIT IS TO BE SETUP AS A DIRECT VENT, THE
MESH SCREEN MUST BE REMOVED. THE INLET VENT PIPE
MAYTHENBEGLUEDTOTHEAIRINTAKE(SeeFigure18B)
PROVIDED ON THE UNIT. THE SCREEN REMOVED FROM THE
INTAKENEEDSTOBEINSERTEDINTOTHE2”-22.5DEGREE
VENT TERMINAL SUPPLIED IN THE VENT TERMINAL KIT.
DIRECT VENT TERMINAL INSTALLATION IMPORTANT
THIS UNIT CONSISTS OF TWO VENT TERMINALS - AN INTAKE
VENT TERMINAL AND AN EXHAUST VENT TERMINAL. THE INTAKE
VENTTERMINALISA2”22.5°PVCELBOW(-)WITHAMESHWIRE
SCREENANDTHEEXHAUSTVENTTERMINALISA2”22.5°PVC
ELBOW WITH A MESH WIRE SCREEN.
NOTE: TO PREVENT EXHAUSTING PRODUCTS FROM
CIRCULATING TO THE AIR INTAKE IN WINDY/COLD AREAS,
THE MAXIMUM PRACTICAL DISTANCE BETWEEN THESE TWO
TERMINALS IS RECOMMENDED.
FIGURE 18C.
WHEN LOCATING THE TERMINALS ON A SIDEWALL, THE
FOLLOWING SPECIFICATIONS PERTAINING TO TERMINAL
LOCATION MUST BE FOLLOWED.
1.Theintakeairterminalandtheexhaustventterminalmustterminate
onthesameexteriorwallandmustbeseparatedbyaminimumof
24”(61cm)onverticalcenterline(seeFigure18C).Incolderclimates
increasing the 24” (61cm) minimum will reduce possibility offrost
overfromsidewindsblowingexhaustvaporstotheairintakeofthe
direct vent.
2.Thehorizontalcenterlineoftheintakeairterminalmaynotbelocated
lowerthanthehorizontalcenterlineoftheexhaustventterminal(see
Figure18C).