- Instruction Manual Residential Gas Water Heater

14
Figures2and10showthetypicalattachmentofthewaterpipingto
thewater heater.Thewaterheater is equipped with 3/4 inchNPT
water connections.
NOTE: If using copper tubing, solder tubing to an adapter
before attaching the adapter to the water heater connections.
Do not solder the water lines directly to the water heater
connections. It will harm the dip tube and damage the
tank.
T & P Valve and Pipe Insulation (if supplied)
Remove insulation for T & P valve and pipe connections from
carton.
FIGURE 11.
Fit pipe insulation over the incoming cold water line and the
hot waterline.Makesurethattheinsulationisagainstthetop
coveroftheheater.FitT&Pvalveinsulationovervalve.Make
sure that the insulation does not interfere with the lever of the
T & P valve.
Secureallinsulationusingtape.
TEMPERATURE-PRESSURE RELIEF VALVE
This heater is provided with a properly certified combination
temperature-pressurereliefvalvebythemanufacturer.
The valve is certiedby a nationallyrecognized testing laboratory
thatmaintainsperiodicinspectionofproductionoflistedequipmentof
materialsasmeetingtherequirementsforReliefValvesforHotWater
SupplySystems,ANSIZ21.22•CSA4.4,andthecoderequirements
of ASME.
Ifreplaced,thevalvemustmeettherequirementsoflocalcodes,but
notlessthanacombinationtemperatureandpressure relief valve
certiedasindicatedintheaboveparagraph.
The valve must be marked with a maximum set pressure not to
exceedthemarkedhydrostaticworkingpressureofthewaterheater
(150psi=1,035kPa)andadischargecapacitynotlessthanthe
water heater
Btu/hr input rate as shown on the water heaters
modelratingplate.
Forsafeoperationofthewaterheater,thereliefvalvemustnotbe
removedfromitsdesignatedopeningnorplugged.
Thetemperature-pressurereliefvalvemustbeinstalleddirectlyinto
thefittingofthewaterheaterdesignedforthereliefvalve.Position
thevalvedownwardandprovidetubingsothatanydischargewill
exitonlywithin6inches(15.2cm)above,oratanydistancebelow
the structural floor. Be certain that no contact is made with any
liveelectricalpart.Thedischargeopeningmustnotbeblocked
orreducedinsizeunderanycircumstances.Excessivelength,
over30feet(9.14m),oruseofmorethanfourelbowscancause
restriction and reduce the discharge capacity of the valve, see
Figures10.
Novalveorotherobstructionistobeplacedbetweentherelief
valveandthetank.Donotconnecttubingdirectlytodischarge
drainunlessa6”(15.2cm)airgapisprovided.Topreventbodily
injury, hazard to life, or property damage, the relief valve must
beallowedtodischargewaterinquantitiesshouldcircumstances
demand.Ifthedischargepipeisnotconnectedtoadrainorother
suitablemeans,thewaterflowmaycausepropertydamage.
TheDischargePipe:
•Shallnotbesmallerinsizethantheoutletpipesizeofthevalve,or
haveanyreducingcouplingsorotherrestrictions.
•Shallnotbepluggedorblocked.
•Shallbeofmateriallistedforhotwaterdistribution.
•Shallbeinstalledsoastoallowcompletedrainageofboththe
temperature-pressurereliefvalve,andthedischargepipe.
•Shallterminateatanadequatedrain.
•Shallnothaveanyvalvebetweenthereliefvalveandtank.