Installation Instructions
4
• Avoid adhesive contact with eyes. Safety glasses should be
worn. If adhesive comes in contact with eyes, flush for 15
minutes and call a physician.
• Care must be taken with fasteners that penetrate the deck to
avoid contact with electrical wiring and plumbing.
• Reroofing over a wet substrate is not good roofing practice.
All wet materials should be removed before proceeding with
the installation of new materials.
• Condensation may occur when applying adhesives at
temperatures below 40
o
F. especially when there is high
humidity. If droplets of water are discovered, discontinue
installation until weather conditions improve. At that time
reapply a thin coat of adhesive over the old coat of adhesive
and continue installation. Note: All adhesives should be
applied at temperatures above 40
o
F. DO NOT ALLOW
ADHESIVE TO FREEZE.
• When using White Membrane Water Based Bonding
Adhesive in a "contact" or two-sided application allow
adhesives to adequately dry to avoid blistering of the
membrane. Note: The RoofKit White Reinforced Membrane
may be applied directly into wet White Membrane Water
Based Bonding Adhesive (one-sided application method)
for horizontal field applications.
• Positive drainage of at least one-eighth inch (1/8") in twelve
inches (12") is required for warranty coverage.
• Petroleum products such as asphalt roof cements and
solvent based coatings will deteriorate the RoofKit White
Reinforced Membrane and should never be used on this
type of roof membrane.
Note: RoofKit White Membrane Water Based Adhesive has
been tested to ensure compatibility with the RoofKit White
Reinforced Membrane. Use of non-RoofKit products will
void the membrane warranty.