Product Manual

TECH 1000 DP
19
en
8.
Data transfer
Multiple-participant mode:
This mode enables multiple participants with different unit addresses but
the same baud rate to connect to the MODBUS.
MODBUS function Description
Query current angle in 1/100°
Query print angle in 1/100°
Software version
Serial number 1
Serial number 2
Change bus address
Switch off measuring unit
Analysis of data connection
protocol
The transmission protocol is configured in accordance with the MODBUS standard.
Characterformat: 1 start bit, 8 data bits, 2 stop bits, no parity
Baud rate:
Default setting: 9600 Bd
Possible: 1200 Bd ... 19,200 Bd
Idle period: at least 3.5 characters between two messages
Unit address:
Default setting: 032
d
Possible: 001
d
….. 247
d
Please note: The data connection is interrupted if there is no query for > 2 seconds.
To prevent errors when analysing measurements, the angle is only transmitted in degrees.
The REF and HOLD settings are deleted.