Instructions / Assembly
Installation 5
LOCATION OF UNIT
Locate the pump as near the liquid source as possible, using a short, direct
suction pipe. Keep the static suction lift (vertical distance between the cen-
ter line of the pump and the liquid level) to a minimum. Mount the pump
on a solid, level foundation, which provides a rigid and vibration-free sup-
port. It should be located where the unit is readily accessible for service
and maintenance. The pump should be protected against flooding and
excessive moisture.
PIPING
Both suction and discharge piping should be independently supported at
a point near the pump to avoid strains being placed on the pump. Start all
piping at pump to avoid strains left by a gap at last connection.
SUCTION PIPING
The suction pipe must be kept free of leaks. The suction pipe must have a
gradual slope upward to the pump. Avoid any fittings which may cause an
air trap. On units that have a suction fitting, a check valve is a built-in fea-
ture and no foot valve is required.
DISCHARGE PIPING
A gate valve and union should be installed in the discharge line. For remov-
al of the pump for service, close the gate valve, and disconnect at union.