G-81
Shield-Kon
®
 Shield Termination System
Wire Termination — Sta-Kon
®
 Wire Termination & Insulation
Installation that’s as easy as 1-2-3!
Mid-Span Method
Enables installation 
anywhere along  
the cable. 
Insulation
Shield Cable
Insulation
Shield
Cable
7
⁄16" (11mm)
7
⁄16" (11mm)
Standard Method
Use the standard method 
when the shielded cable  
or the inner conductors are 
embedded in a dielectric.
Fold-Back Method 1
If there is no common 
dielectric for several interior 
cables but the gaps are 
filledby textile threads 
orsomething similar, care 
should be taken to ensure 
that the insulating thick ness 
of the individual cables is not 
less than .38mm for PVC, 
and not less than .25mm 
for Teflon. If this insulation 
thickness falls below this 
value, Fold-Back Method 1 
should be used.
Fold-Back Method 2
Fold-Back Method 2 should 
be used if the cable shield 
is applied spirally or if 
afoilshield is being used.
Installation Methods
Installation Procedure
Connector opening faces  
away from tool
Step 3
Select the appropriate die set for the 
crimp tool, according to the size of  
the shielded cable (see page G-80) 
and mount the dies on the tool.  
Insert the connector (with the shielded 
cable and the ground wire) between  
the dies of the tool.
Squeeze the tool handles firmly to crimp 
the connector around  
the shielding and  
the ground wire.
Shield
Conductors
Jacket
Insulation
1
⁄4" (6mm)
Butt insulating jackets 
against metal edge
Insulation
Shield
Cable
Insulation
Shield
Cable
Step 1
Prepare shielded wire and ground wire insulation as shown. 
If two ground wires are required in a Shield-Kon
®
 connection,  
twist both conductors before insertion into the connector.
Step 2
Select the appropriate connector according to the size of the shielded  
cable (see page G-80). Place the ground wire around the trap hook and  
the shielded wire into the bottom of the connector. 
When inserting the shielded cable and grounding wire, care must be taken 
to ensure that their insulation is overlapped by the connector’s Polyester 
insulation film.
100% insulation is possible after crimping when the stripped length  
of outer jacket (visible shielding) is 
7
⁄16" (11mm) maximum.
For a complete listing of One-Piece 
Connectors, see page G-80.
For a complete listing of One-Piece 
Connector Dies, see page G-80.