Service Entry Requirements Class 3130 / 3110
Service Entry Requirements
USA and Mexico
Switches not factory bonded are shipped suitable for use as service equipment.
Switches that are shipped from the factory with a bonded neutral are suitable only for
use as service equipment.
Enclosure must be grounded via the ground terminal.
Devices require line side barriers.
Devices need neutral kit installed.
Bonding Screw must be driven into enclosure; bonding the insulated neutral to the
enclosure. The enclosure must be ground using the ground terminal.
Canada
Switches that are shipped from the factory with a bonded insulted neutral are suitable
for use as service equipment. The enclosure must be grounded using the ground
terminal.
Devices require line side barriers.
NOTE: Canada factory bonded insulated neutral can be un-bonded and used for
other applications other than the service entrance.
GEX75737 23