Instructions / Assembly

Class 3130 / 3110 Line Side Barriers
Line Side Barriers
General duty and heavy duty single throw units 30, 60, 100, and 200 A switches are
design to provide protection from inadvertent contact on incoming terminals. Internal
components comply with IP2X ratings and UL 869A .
Field Installed barriers are available for 400, 600, 800, and 1200 A devices and when
installed, provide protection from inadvertent contact on incoming terminals.
Ampere
Product
Voltage Rating AC
Two Pole Three Pole
400
Heavy Duty
240 LSBG202 LSBG203
600 LSBG602 LSBG602
600
240 LSBG202 LSBG203
600 LSBG602 LSBG602
800
240 LSBF202 LSBF203
600 LSBF602 LSBF602
1200
240 LSBF202 LSBF203
600 LSBF602 LSBF602
Wire insulation is part of the touch protective system, the tables below give the
amount of conductor that should be exposed.
Figure 1 - Stripped
Wire
Table 7 - General Duty Safety Switches
Ampere Voltage Wire Strip
30
240
0.47 in. / 12 mm
60
100 0.60 in. / 15 mm
200 0.87 in. / 22 mm
400
1.25 in. / 32 mm600
800
Table 8 - Heavy Duty Safety Switches
Ampere Voltage Wire Strip
30
240
0.47 in. / 12 mm
60
100 0.60 in. / 15 mm
200 0.87 in. / 22 mm
400
1.50 in. / 38 mm
600
800
1.50 in. / 38 mm (top) 2.70 in. / 69 mm (bottom)
1200
30
600
0.47 in. / 12 mm
60
0.60 in. / 15 mm
100
200 0.87 in. / 22 mm
400
1.50 in. / 38 mm
600
800
1.50 in. / 38 mm (top) 2.70 in. / 69 mm (bottom)
1200
22 GEX75737