Instructions / Assembly

Non-Fusible Safety Switch Short Circuit Current Rating Class 3130 / 3110
Non-Fusible Safety Switch Short Circuit Current
Rating
Table 6 - Non-Fusible Safety Switches, NEMA Type 7/9 SCCR 10 kAIR 600 Vac maximum
Switch Rating
(A)
Fuse or Circuit
Breaker Type
10
240 Vac 480 Vac 600 Vac 250 Vdc
Switch Ratings
(A)
With Upstream Fuse
Protection
240 Vac 480 Vac 600 Vac 250 Vdc/ 600 Vdc
ALL
H, K
10 kA 10 kA 10 kA
up to 10 kA
R, T, J, L
200 kA 200 kA 200 kA
up to 10 kA
Switch Ratings
(A)
With Upstream Circuit
Breaker Protection
240 Vac 480 Vac 600Y/347 Vac 250 Vdc
30, 60, 100
BD 25 kA 18 kA 14 kA
up to 10 kA
30, 60, 100
BG 65 kA 35 kA 18 kA
up to 10 kA
30, 60, 100
BJ 100 kA 65 kA 25 kA
up to 10 kA
30, 60, 100
BK 100 kA 65 kA 65 kA
up to 10 kA
Switch Ratings
(A)
With Upstream Circuit
Breaker Protection
240 Vac 480 Vac 600 Vac 250 Vdc
ALL
Any brand circuit
breaker
10 kA 10 kA 10 kA
up to 10 kA
30, 60, 100
HD 25 kA 18 kA 14 kA
up to 10 kA
30, 60, 100
HG 65 kA 35 kA 18 kA
up to 10 kA
30, 60, 100
HJ 65 kA 35 kA 18 kA
up to 10 kA
30, 60, 100
HL 65 kA 35 kA 35 kA
up to 10 kA
30, 60, 100
HR 65 kA 35 kA 35 kA
up to 10 kA
30, 60, 100
FA 14 kA 14 kA 14 kA
up to 10 kA
30, 60, 100
FH 18 kA 18 kA 18 kA
up to 10 kA
200
HD, JD
25 kA 18 kA 14 kA
up to 10 kA
200
HG, JG
65 kA 35 kA 18 kA
up to 10 kA
200
HJ, JJ
65 kA 65 kA 25 kA
up to 10 kA
200
HL, JL
65 kA 35 kA 35 kA
up to 10 kA
200
HR, JR
65 kA 35 kA 35 kA
up to 10 kA
400 LA 25 kA 25 kA 25 kA
up to 10 kA
400 LH 25 kA 25 kA 25 kA
up to 10 kA
400, 600
LD 25 kA 18 kA 14 kA
up to 10 kA
400, 600
LG 65 kA 35 kA 18 kA
up to 10 kA
400, 600
LJ 100 kA 65 kA 25 kA
up to 10 kA
400, 600
LL 100 kA 65 kA 50 kA
up to 10 kA
400, 600
LR 100 kA 65 kA 65 kA
up to 10 kA
GEX75737 19
10. Ampere rating of fuse or circuit breaker not to exceed switch ampere rating.