Installation Class 3130 / 3110
Table 2 - Anchorage As-Tested (Continued)
Type 12 and Type 4X 30, 60, 100 A 240 V / 600 V
1/4 in. grade 5 bolts and flat washer at four locations,
torque to 7 ft–lbs. Top and bottom outside holes.
Type 1 and Type 3R 60 A 240V 100 A 240 V / 600 V
1/4 in. grade 5 bolts and flat washer at four locations,
torque to 7 ft–lbs.
Type 1 and Type 3R 200 A 240 V / 600 V
1/4 in. grade 5 bolts and flat washer at four locations,
torque to 7 ft–lbs.
Type 12 and Type 4X 100 and 200 A 240 V / 600 V
1/4 in. grade 5 bolts and flat washer at four locations,
torque to 7 ft–lbs.