Instructions / Assembly
Table Of Contents
- Square D™ Safety Switch User Manual
- Safety Information
- Installation and Operation Requirements
- Exposure to Moisture, Chemicals, and Condensation
- Installation
- Fusible Safety Switches
- Class R Rejection Clip Kits
- Non-Fusible Safety Switch Short Circuit Current Rating
- Ground Kits
- Insulated Neutral Assemblies
- Line Side Barriers
- Service Entry Requirements
- Maintenance
- Wiring Diagrams
- Replacing the Viewing Window 30–200 A
Class 3130 / 3110 Installation
Seismic Certifications
Equipment Installation for Seismic Applications
Introduction
Seismic certification is an optional feature for Safety Switch products and provides
seismic conformance options to any of the building codes and seismic design
standards identified in the List of Supported Regional Building Codes and Seismic
Design Standards, page 10. Safety Switches that are seismically certified have been
certified to the seismic requirements of the listed code per the manufacturer’s
Certificate of Compliance (CoC). Equipment compliance labels and CoC’s are
provided with all seismically certified Safety Switches. Refer to the equipment CoC for
certification details and applicable seismic parameters. To maintain the validity of this
certification, the installation instructions provided in this section must be followed.
Table 1 - List of Supported Regional Building Codes and Seismic Design Standards
Country / Region
Code Reference ID Code Name
Argentina
INPRES-CIRSOC103
Argentinean Standards for Earthquake Resistant Constructions
Australia
AS 1170.4-2007 (R2018) Structural design actions, Part 4: Earthquake actions in Australia
Canada NBCC
National Building Code of Canada
Chile NCh 433.Of1996
Earthquake resistant design of buildings
China
GB 50011-2010 (2016) Code for Seismic Design of Buildings
Colombia NSR-10 Título A
Colombian Regulation of Earthquake Resistant Construction
Europe
Eurocode 8 EN1998-1
Design of structures for earthquake resistance – Part 1: General rules, seismic
actions and rules for buildings
India
IS 1893 (Part 1) : 2016
Criteria for Earthquake Resistant Design of Structures Part 1 General
Provisions and Buildings
Indonesia SNI 1726:2019
Earthquake Resistance Planning Procedures for Building and Non-building
Structures
Japan Building Standard Law The Building Standard Law of Japan
Mexico CFE MDOC-15
Civil Works Design Manual, Earthquake Design
New Zealand NZS 1170.5:2004+A1
Structural design actions, Part 5: Earthquake actions – New Zealand
Peru N.T.E. - E.030
National Building Code, Earthquake-Resistant Design
Russia СП 14.13330.2018
Building norms and regulations: Construction in seismic regions
Saudi Arabia SBC 301
Saudi Building Code, Loads & Forces Requirements
Taiwan CPA 2011
Seismic Design Code and Commentary for Buildings
Turkey
TBEC-2018
Turkey Buildings Earthquake Standard
United States
IBC per ASCE 7 International Building Code—IBC
CBC per ASCE 7 California Building Code—CBC
UFC per DoD
Uniform Facilities Criteria—UFC
Responsibility for Mitigation of Seismic Damage
The Safety Switch equipment is considered a non-structural building component as
defined by regional building codes and seismic design standards. Equipment capacity
was determined from tri-axial seismic shake-table test results in accordance with the
International Code Counsel Evaluation Service (ICC ES) Acceptance Criteria for
Seismic Certification by Shake-Table Testing of Nonstructural Components (ICC-ES
AC156).
10 GEX75737