Technical Data Bulletin

2-6
© 2019 Schneider Electric
All Rights Reserved
MP Meter-Pak™ Meter Centers
Ring and Ringless Devices
schneider-electric.us
Class 4141 / Refer to Catalog 4100CT0701
Table 2.10: Ring Type MP Meter-Pak Metering Equipment with 125 A (42 kA Maximum SCCR) or 200 A (22 kA Maximum SCCR) Meter
Socket Positions
Amperes
per Pos.
No. of
Positions
Factory-Installed
Main Lugs
Ampacity
(alternate lugs [1])
Main Bus
Ampacity
(A)
Cat. No.
Line Lug Wire
Size Al/Cu
AWG/kcmil
Circuit
Breaker Type
(2P)
Hub Prov. [2]
Semi-Flush
Flange Kit
Wt Lbs
Box
No.
125
2 200 200
MP22125 [3] (1) 4–250
QO,
QO-VH,
QOH
A/B300 MPSF12 46 1R
3 300 300
MP33125 [4]
(1) 1/0–600 or
(2) 1/0–250
A-L MPSF14 95 2R
4 400 400
MP44125 [4]
(1) 1/0–600 or
(2) 1/0–250
A-L MPSF14 97 2R
5
400 Al
500 Cu
500
MP55125 [4]
(1) 1/0–600 or
(2) 1/0–250
(4) A-L
MPSF16 130 3R
6
400 Al
500 Cu
600
MP66125 [4]
(1) 1/0–600 or
(2) 1/0–250
(4) A-L
MPSF16 132 3R
200
2 400 400
MP42200 [4]
(1) 1/0–600 or
(2) 1/0–250
QOM2-MM,
QOM2-MVH
(4) A-L
MPSF23 99 4R
3 400 400
MP43200 [4]
(1) 1/0–600 or
(2) 1/0–250
MPSF23 99 4R
4 400 600
MP64200 [4]
(1) 1/0–600 or
(2) 1/0–250
MPSF24 135 5R
5
600 Al, 750 Cu
800
MP85200 [4] (2) 3/0–500
MPSF26 173 6R
6
600 Al, 750 Cu
800
MP86200 [4] (2) 3/0–500
MPSF26 173 6R
Table 2.11: Ringless Type MP Meter-Pak Metering Equipment with 125 A (42 kAMaximum SCCR) or 200 A Type MPR, MPH (22 kA
Maximum SCCR) or 225 A Type MPL (100 kA Maximum SCCR) Meter Socket Positions
Amperes
Per
Pos.
No.
of
Pos.
Factory-Installed
Main Lugs
Ampacity
(alternate lugs [1])
Main Bus
Ampacity
No. Bypass
Cat. No.
Horn
Bypass
Cat. No.
Lever
Bypass
Cat. No.
Line Lug
Wire Size
Al/Cu
AWG/kcmil
Circuit Breaker
Type
(2P)
[5].
Hub
Prov. [2]
Semi-Flush
Flange Kit
Wt
Lbs
Box
No.
125
2 200 200 MPR22125 MPH22125
(1) 4–250
QO,
QO-VH,
QOH
A/B300 MPSF12 46 1R
3 300 300 MPR33125 MPH33125
(1) 1/0–600 or
(2) 1/0–250
A-L
MPSF14 95 2R
4 400 400 MPR44125 MPH44125
(1) 1/0–600 or
(2) 1/0–250
MPSF14 97 2R
5
400 Al
500 Cu
500 MPR55125 MPH55125
(1) 1/0–600 or
(2) 1/0–250
(2) A-L
MPSF16 130 3R
6
400 Al
500 Cu
600 MPR66125 MPH66125
(1) 1/0–600 or
(2) 1/0–250
MPSF16 132 3R
200
2 400 400 MPR42200 MPH42200
(1) 1/0–600 or
(2) 1/0–250
QOM2-MM,
QOM2-MVH
(2) A-L
MPSF23 99 4R
3 400 400 MPR43200 MPH43200 MPSF23 99 4R
4 400 600 MPR64200 MPH64200 MPSF24 135 5R
225
2 350 350 MPL32225
(1) 1/0–600 or
(2) 1/0–250
QBP-TM,
QDP-TM,
QGP-TM or
QJ-TM
QO [6],
QO-VH [6]
or QOH [6]
N/A 105 7R
3 400 500 MPL53225 N/A 147 8R
4 400 600 MPL64225 N/A 200 9R
200
5
600 Al, 750 Cu
800 MPR85200 MPH85200
(2) 3/0–500
QOM2-MM,
QOM2-MVH
MPSF26 173 6R
6
600 Al, 750 Cu
800 MPR86200 MPH86200
(2) 3/0–500
MPSF26 173 6R
NOTE: UL Listed short circuit current rating depends on lowest interrupting rating of
circuit breaker installed.
2
METERING EQUIPMENT
[1] See page 2-7 for alternate lugs.
[2] For A and A-L Hubs see page 2-3, for B Hubs see Digest Section 3.
[3] Meets EUSERC standards.
[4] Meets EUSERC standards with addition of lug landing kit, MMSK2.
[5] See page 2-7
[6] Requires use of EZM125QOA adapter (order separately).
5/15/2019