Technical Data Bulletin

© 2019 Schneider Electric
All Rights Reserved
2-3
schneider-electric.us
Horizontal Ganged, Test Block Bypass
Sockets and Accessories
Meter Sockets
Class 4131 / Refer to Catalog 4100CT0701
Horizontal Ganged Meter Sockets
UT2R1121B
1Ø, 600 Vac max., main lugs only, 2 through 6 meter positions, with and without
horn or lever bypass, end or center feed, overhead and underground service feeds.
10 kA short circuit current rating (or higher with utility approval).
UL Listed, NEMA 3R enclosure.
Supplied with ground lugs.
Supplied with hub opening in top endwall, requires the use of a bolt-on hub, or closing
plate.
This metering is generally utility specific. Always check with local utility company
before installing. Contact your nearest Field Sales Office for additional catalog
numbers, if required by utility.
Table 2.2: Ringless Type, 1Ø3W, 600 Vac Max., Without Bypass or Jaw Release
Branch Ratings
Mains
Rating
(A)
Cat. No.
Main Lugs
Phase and Neutral
Al/Cu
(AWG/kcmil)
Branch Lugs
Phase and Neutral
Al/Cu (AWG)
Top Endwall [12]
Box No. [13]
Amperes
[14]
No. of
Positions
Socket
Jaw
Qty. [15]
Service
Type
Hub Type
(Order
Separately)
Closing Plate
(Order
Separately)
100 A
2
4 OH/UG
200 UT2R1121B 6–250
8–2/0 Series A ACP
13R
3 205 UT3R1121B 6–250  13R1
4 205 UT4R1131B 6–350 14R
5 250 UT5R1131B 6–350 15R
6 300 UT6R1131B 6–350 16R
200 A
2
4 OH/UG
205 UT2R2122B 6–250
8–250
Series A ACP 17R
4 360 UT4R2352T 1/0–500 Series A-L ACPL 18R
5 500 UT5R2392TU
1/0–500 or
Series A-L ACPL 19R
(2)1/0–350
6 620 UT6R2392TU
1/0–500 or
Series A-L ACPL 20R
(2)1/0–350
Meter Mains with Test Block Bypass
EMT3225CB
EMT1225CB
Without Covers
Table 2.3: Ring Type, 1Ø3W and 3Ø4W, Meter Main with Test Block Bypass (Meets
EUSERC Requirements)
System (Incoming)
and
Service (Outgoing)
Meter
Socket
Type
Ampere
Rating
(Max.)
Short
Circuit
Current
Rating
Cat. No. [13][16]
Main Circuit Breaker Type
(Order Separately) [17]
120/240 Vac 1Ø3W 5-Jaw 225 A
100 kA
max.
EMT1225CB
2P Type QB, QD, QG, QJ
(QO, QO-VH, QOH) [18]
208Y/120 Vac 3Ø4W[19]
or
240/120 Vac 3Ø4W
Delta
7-Jaw 225 A 65 kA max. EMT3225CB
3P Type QB, QD, QG or QJ
Table 2.4: EMT Terminal Wire Size [20]
Line Phase Lug Line Neutral Lug Service Ground Lug Equipment Ground Lug Load Neutral Lug
6 AWG–300 kcmil
Al/Cu
6 AWG–350 kcmil
Al/Cu
4 AWG–300 kcmil
Al/Cu
6 AWG–300 kcmil
Al/Cu
4 AWG–300 kcmil
Al/Cu
Meter Socket Accessories
Table 2.5: Adapter Plate, Lug Kits,
and Sealing Rings
Accessory Description
Cat. No.
Adapter
Plate
To allow the use of a Series A Hub on a
device that is setup for a series A-L
Hub.
AAP
Lug Kits
For use on meter sockets supplied with Line, Load, and
Neutral Studs only. Be sure to order enough lugs for
each device (a typical device requires 6 lugs).
Includes one, two-barrel lug (6-250
kcmil)
ARP00118
Includes one, single barrel lug (4-600
kcmil)
ARP00129
Includes three, two-barrel lugs (6-350
kcmil)
ARP00427
Sealing
Ring
Snap-on Aluminum (Standard)
2920910001
Snap-on Stainless Steel (Non-standard)
ARP00026
Screw Type Aluminum (Non-standard)
29008W
Table 2.6: Fifth-Jaw Kit, Closing Plates, and Hubs
Accessory Description
Cat. No.
Fifth-Jaw Kit
Converts a 4-jaw meter socket to a 5-jaw meter socket. For use on
meter sockets supplied without lever bypass or jaw release only.
A5J
Closing Plates
(to seal hub openings)
For Series A (steel)
ACP
For Series A (aluminum)
ACPA
For Series A-L (steel)
ACPL
For Series A-L (aluminum)
ACPLA
Hubs
(listed by
conduit size)
Series A
1.00 inch A100
1.25 inch A125
1.50 inch A150
2.00 inch A200
2.50 inch A250
Series A-L
2.00 inch A200L
2.50 inch A250L
3.00 inch A300L
3.50 inch A350L
4.00 inch A400L
Series B 3.00 inch B300
2
METERING EQUIPMENT
[12] For hubs and closing plates, see page 2-3.
[13] For box dimensions, see page 2-4
[14] Rating is continuous.
[15] Fifth jaw kit available to convert 4-jaw socket to a 5-jaw socket. See page 2-3.
[16] Supplied with bondable neutral, suitable for use as service equipment , suiteable for overhead or underground service. UL Listed E6294.
[17] See page 2-21 to select main circuit breaker.
[18] Requires use of an EZM125QOA adapter (order separately), when using QO (40 A–125 A, 2-pole) 10 kA max. SCCR, QO-VH (40 A–60 A, 2-pole) 22 kA max. SCCR, or QOH (40 A–60 A,
2-pole) 42 kA max. SCCR.
[19] 100 kA max.
[20] Refer to circuit breaker listings for usable load lug wire sizes.
5/15/2019