Technical Data Bulletin

2-24
© 2019 Schneider Electric
All Rights Reserved
Enclosures
Enclosed Switches, Dimensions, and
Accessories
schneider-electric.us
Class 610
Enclosed Molded Case Switches
Enclosed molded case switches are UL Listed devices supplied with factory-installed
automatic molded case switch. Use the Cat. No. listed below and add the enclosure
NEMA type suffix as noted in footnote in Table 2.39. An insulated groundable neutral, if
required, must be ordered separately from Digest Section 7. Enclosed molded case
switches are manufactured on order only.
Table 2.39: Enclosed Molded Case Switches
System
Ampere
Rating
Cat. No.
Add Suffix [1]
600 Vac
Short Circuit
Withstand Ratings
LH—400 A Frame, 3P, 600 Vac Max.
2P 400
LHE26000( )
25 kA
3P 400
LHE36000( )
25 kA
NEMA Type 1
NEMA Type 3R
W
H
D
NEMA Type 4, 4X, 5, 12, 12K
Table 2.40: Enclosed Molded Case Switch Dimensions
Cat. No.
Prefix—Suffix
Approximate Dimension
Series
H W D
in. mm in. mm in. mm
LHE—AWK E05 42.25 1073 13.75 349 7.25 184
LHE—DS E05 42.25 1073 13.75 349 7.25 184
LHE—F A03 45.63 1159 16.50 419 6.50 165
LHE—R A03 44.00 1118 15.38 391 7.88 200
LHE—S E03 44.50 1130 15.38 391 6.50 165
Lock-On Provisions
Lock-on Provision
Lock-On Provision
Lock-off provisions are standard on all NEMA Type 4, 4X, 5 stainless steel and NEMA
Type 12, 12K circuit breaker enclosures. Provision for one inch hasp padlock is available
factory installed. This modification will allow the circuit breaker to be locked in the ON
position. When locked in the ON position, the external operator will not indicate if circuit
breaker is tripped. UL Listed.
Table 2.41: Enclosure
Enclosure Prefix Suffix for Lock-On Provision
FA, J, LA, L, M, P
SPLO
Pilot Light—Selector Switch—Push Button
Pilot lights, push buttons or selector switches are available factory installed in the cover
of NEMA Type 4, 4X, 5 stainless steel or NEMA Type 12, 12K circuit breaker enclosures.
Wiring to contact blocks is not available. Customer must furnish catalog number of
device desired. Price = circuit breaker + enclosure + neutral + ground + pilot light, push
button and/or selector switch + factory-installed adder. Order by description. L600
enclosures are UL Listed, other enclosures are not UL Listed.
Phenolic Legend Plate
Available engraved and mounted on most circuit breaker enclosures. Legend engraved
in 1/4-inch high white letters on black background. Customer must provide legend. UL
Listed. Not available on NEMA Type 7 or 9 enclosures.
To order, add suffix NP to standard catalog number (i.e. LA400SNP).
Stainless Steel Front Enclosure
The FA100F NEMA Type 1, flush-mount circuit breaker enclosure is available with a
stainless steel front. This modification is desirable in food handling areas such as
cafeterias and restaurants. Not UL Listed.
Table 2.42: Stainless Steel Front Enclosure
Cat. No.
FA100FSS
2
METERING EQUIPMENT
[1] Add suffix S or F for NEMA 1 surface mounted or NEMA 1 flush mounted, respectively. Add suffix RB for NEMA 3R with bolt-on hub provision (FHE prefix only) or suffix R for NEMA 3R with
a blank top endwall (LHE prefix only), respectively. Add suffix AWK for NEMA 12. Add suffix DS for NEMA 4/4X/5 stainless steel.
5/15/2019