Technical Data Bulletin
2-16
© 2019 Schneider Electric
All Rights Reserved
EZ Meter-Pak™ Meter Centers
3 Phase Main Devices
schneider-electric.us
Class 4162 / Refer to Catalog 4100CT0701
Table 2.23: 3Ø Main Devices, EUSERC
Ampere
Rating
Service
Feed
Horizontal Cross
Bus Rating and Bus
Bar Material
Cat. No.
Width
(in.)
Factory-Installed Lug Landings For
use with Crimp-Type Lugs (2-Hole
Mounting) Qty. per Phase and
Neutral, except non-EUSERC device.
[38]
EZM31200GCBEMS
Main Circuit Breakers (3Ø Incoming and 3Ø Outgoing)
Short Circuit Rating
65 kA 100 kA
400 UG
400 A, Al
EZM3400CBU [39]
— 20.46
1 (Order Lugs Separately)
600 UG
600 A, Al
EZM3600CBU[39]
— 26.19
2 (Order Lugs Separately)
800 UG
800 A, Al
EZM3800CBU [39]
— 26.19
2 (Order Lugs Separately)
1000 UG
1200 A, Cu
EZM31000CBU — 34.19
3 (Order Lugs Separately)
1200 UG
1200 A, Al
EZM31200GCBE [40] EZM31200JCBE [40]
32.39
3 (Order Lugs Separately)
Main Fusible Switches (3Ø Incoming and 3Ø Outgoing) Requires 300 Vac Class T Fuses (Order Separately)
400 UG
400 A, Al
— EZM3400FSU 20.46
1 (Order Lugs Separately)
600 UG
600 A, Al
—
EZM3600FSU
26.19
2 (Order Lugs Separately)
800 UG
800 A, Al
—
EZM3800FSU
26.19
2 (Order Lugs Separately)
1200 UG
1200 A, Al
— EZM31200FSE 32.39
3 (Order Lugs Separately)
Main Lugs Terminal Boxes (3Ø Incoming and 3Ø Outgoing)
400 UG
400 A, Al
—
EZM3400TBU [41]
17.16
1 (Order Lugs Separately)
800 UG
800 A, Al
—
EZM3800TBU [41]
25.16
2 (Order Lugs Separately)
1200 UG
1200 A, Cu
—
EZM31200TBU [41]
33.16
3 (Order Lugs Separately)
Main Circuit Breaker (3Ø Incoming and 3Ø Outgoing) with Energy reduction Maintenance Switch (ERMS)
1200 UG
1200 A, Cu
EZM31200GCBEMS EZM31200JCBEMS 32.39
3 (Order Lugs Separately)
2
METERING EQUIPMENT
[38] For mechanical lugs (3/0 AWG– 600 kcmil) order kit CMELK4. Kit includes 4 lugs only. Multiple kits may be required, consult factory. For crimp-type lugs refer to Anderson Electrical
Connector Products Catalog AEC-40R.
[39] Available by special order with main circuit breaker supplied with other standard ampere ratings, consult your nearest Field Sales Office (allow 6 weeks for delivery).
[40] Ampere rating of the circuit breaker supplied with this device can be changed to a LOWER value in the field by changing the setting on the circuit breaker.
[41] Terminal box is suitable for use on LINE or LOAD side of service equipment. Supplied with isolated neutral and provided with neutral bonding kit for use as required. Refer to page 2-11 for
appropriate short circuit current ratings.