3 Phase Main Devices
EZ Meter-Pak™ Meter Centers
Class 4162 / Refer to Catalog 4100CT0701
3Ø4W 208Y/120 Vac or 240/120 Vac Delta EZ Meter-Pak™ Meter
Centers—3Ø Indoor/Rainproof, UL Listed
1200 A Main CB/Fusible Switch Devices come Standard with 2-STEP Removable
Service Entrance Endwalls
Select EZM meter center short circuit current rating from Table 2.16. Using this table as a
reference, make the following selections:
1. Select 3Ø EZM main device below with an equal or higher short circuit rating than
the application from Table 2.22 and Table 2.23.
2. Select EZM 3Ø branch units from , Table 2.25, and Table 2.26.
3. Select proper 2P type QO, QO-VH, QOH, QBP-TM, QDP-TM, QGP-TM or QJP-TM
or 3P QBP-TM, QDP-TM, QGP-TM or QJP-TM branch circuit breakers for use as
tenant mains in branch unit; from Table 2.33 and Table 2.34.
4. Select accessories as required, from page 2-21.
5. Dimensions see page 2-22.
3 Phase Main Devices—NEMA 3R Construction
Table 2.22: 3Ø Main Devices
Ampere
Rating
Service
Feed
Horizontal Cross
Bus Rating and Bus
Bar Material
Cat. No.[31]
Width
(in.)
Factory-Installed Line Side
Lug (Conductors per Phase
and Neutral) Wire Size (AWG–
kcmil)
EZM31200FST
Main Circuit Breakers (3Ø Incoming and 3Ø Outgoing)
65 kA Short Circuit Current Rating (400–1600 A Max.), 100 kA Short Circuit Current Rating (2000 A Max.)
Short Circuit Rating
65 kA 100 kA
400 OH/UG
400 A, Al
EZM3400CB — 18.66
(1) 1–600 or (2) 1–250
600 OH/UG
600 A, Al
EZM3600CB — 18.66
(3) 3/0–500
800 OH/UG
800 A, Al
EZM3800CB — 18.66
(3) 3/0–500
1000 OH/UG
1200 A, Al
EZM31000CB — 18.66
(3) 3/0–500
1200 OH
1200 A, Al
EZM31200GCBT [32] EZM31200JCBT [32]
23.69
(4) 3/0-500
1200 UG
1200 A, Al
EZM31200GCBU [33] [32] EZM31200JCBU [33] [32]
23.69
(4) 3/0-500
1600 OH/UG
1200 A, Al/Cu
EZM31600GCBC[32] [34] EZM31600JCBC[32] [34]
30.19
(6) 1/0–750 or (12) 1/0–250
1600 UG
1200 A, Al/Cu
EZM31600GCBU [32][34] EZM31600JCBU [32][34]
30.19
6 (Order Lugs Separately)
2000 OH/UG
1200 A, Al/Cu
—
EZM32000CB [34]
30.19
(6) 1/0–750 or (12) 1/0–250
2000 UG
1200 A, Al/Cu
—
EZM32000CBU [34]
30.19
6 (Order Lugs Separately)
Main Fusible Switches (3Ø Incoming and 3Ø Outgoing) Requires 300 Vac Class T Fuses (Order Separately)
400 OH/UG
400 A, Al
— EZM3400FS 18.66
(1) 1–600 or (2 )1–250
600 OH/UG
600 A, Al
— EZM3600FS 18.66
(3) 3/0–500
800 OH/UG
800 A, Al
— EZM3800FS 18.66
(3) 3/0–500
1200 OH
1200 A, Al
— EZM31200FST 23.69
(4) 3/0–500
1200 UG
1200 A, Al
—
EZM31200FSB [33]
23.69
(4) 3/0-500
Main Lug Terminal Boxes (3Ø Incoming and 3Ø Outgoing)
225 OH/UG
800 A, Al
—
EZM3225TB [35]
11.66
(1) 4–300
400 OH/UG
800 A, Al
—
EZM3400TB [36]
17.15
(2) 3/0–500
600 OH/UG
800 A, Al
—
EZM3600TB [36]
17.15
(2) 1/0–750 or (4) 1/0–300
800 OH/UG
800 A, Al
—
EZM3800TB [36]
18.66
(4) 3/0–500
800 OH/UG
800 A, Cu
—
EZM3800TBCU [36] [37]
24.08
(4) 3/0–500
1600 OH/UG
1200 A, Al/Cu
—
EZM31600TB [34] [37] [36]
22.48
(6) 1/0-600 or (12) 1/0-300
2000 OH/UG
1200 A, Cu
—
EZM32000TB [36]
30.19
6 (Order Lugs Separately)
Main Circuit Breakers (3Ø Incoming and 3Ø Outgoing) with Energy Reduction Maintenance Switch (ERMS)
1200 OH
1200 A, Cu
EZM31200GCBTMS EZM31200JCBTMS 23.69
(4) 3/0–500
1200 UG
1200 A, Cu
EZM31200GCBUMS EZM31200JCBUMS 23.69
(4) 3/0–500
1600 OH/UG
1200 A, Cu
EZM31600GCBCMS EZM31600JCBCMS 30.19
(6) 1/0–750 or (12) 1/0–250
1600 UG
1200 A, Cu
EZM31600GCBUMS EZM31600JCBUMS 30.19
6 (Order Lugs Separately)
2000 OH/UG
1200 A, Cu
EZM32000CBMS — 30.19
(6) 1/0–750 or (12) 1/0–250
2000 UG
1200 A, Cu
EZM32000CBUMS — 30.19
6 (Order Lugs Separately)
2
METERING EQUIPMENT
[31] Does not meet EUSERC requirements.
[32] Ampere rating of the circuit breaker supplied with this device can be changed to a LOWER value in the field by changing the setting on the circuit breaker.
[33] For field installed Lug Landing Kit order catalog number EZM1200ULL.
[34] Supplied with copper horizontal bus bars and aluminum vertical bus bars.
[35] 225 A terminal box supplied with isolated neutral that cannot be bonded.
[36] Terminal box is suitable for use on LINE or LOAD side of service equipment. Supplied with isolated neutral and provided with neutral bonding kit for use as required. Refer to page 2-11 for
appropriate short circuit current ratings.
[37] Feed-thru lug kit available, see Table 2.35