Technical Data Bulletin
© 2019 Schneider Electric
All Rights Reserved
2-11
schneider-electric.us
Selection Information EZ Meter-Pak™ Meter Centers
Class 4141 / Refer to Catalog 4100CT0701
Selection Information
•
Review local utility
requirements to ensure that
metering equipment meets
their standards.
•
Check local utility to determine
available fault current at the
meter center.
•
Using the SCCR table:
– Select meter center configuration, main lugs only (Six Disconnect Rule), or remote main, main circuit
breaker, or main fusible switch.
– Read down to select SCCR equal to, or greater than desired rating.
– Read across to select branch unit tenant circuit breaker type.
– Continue reading across to select EZM main device type.
Table 2.16: UL Listed Meter Center Short Circuit Current Ratings (SCCR)
[1]
Figures
Short Circuit
Current Rating
(240 Vac
Maximum) [2]
[3]
EZM Meter Center Overcurrent Protection Devices
EZM Branch Unit Tenant Circuit Breaker
Types Available (Branch Unit Amperes
max.,
Number of Poles, Tenant Circuit Breaker
Amperes Rating Range)
EZM Main Device with Integral Mounted Main, Remote Mounted Main
or without an Upstream Mounted Main (Six Disconnect Rule)
EZM Branch Units
Service
Disconnects
(6 Max.)
Transformer
Load
Centers
(Main Lugs)
EZM Main Lugs
Terminal Box
Figure 1 [4]
EZ Meter-Pak (Six Disconnect Rule Applications)—See Figure 1
10 kA
QO (125 A, 2P, 40–125 A)
QO (225 A, 2P, 40–125 A) [5]
QB (225 A, 2P or 3P, 70–225 A)
400–2000 A Main Lugs Terminal Box
(Tenant Circuit Breakers used as Service Disconnects—6 maximum)
22 kA
QO-VH (125 A, 2P, 40–125 A )
QO-VH (225 A, 2P, 40–60 A) [5]
25 kA
QD (225 A, 2P or 3P, 70–225 A)
42 kA
QOH (125 A, 2P, 40–125 A)
QOH (225 A, 2P, 40–60 A) [5]
65 kA
QG (225 A, 2P or 3P, 70–225 A)
100 kA
QJ (225 A, 2P or 3P, 70–225 A) [6]
LJL (125–400 A, 2P or 3P) [7]
EZM Branch Units
Upstream Disconnection
Means and Overcurrent
Protection as Required
Transformer
Load
Centers
(Main Lugs)
Tenant
Circuit
Breakers
EZM Main Lugs Terminal Box
Figure 2 [4]
EZ Meter-Pak 225–2000 A Main Lugs Terminal Box Applications Protected by Remote Main—See Figure 2
10 kA
QO (125 A, 2P, 40–125 A)
QO (225 A, 2P, 40–125 A) [5]
QB (225 A 2P or 3P, 70–225 A)
LJL (125–400 A, 2P or 3P) [7]
Must be protected by an upstream disconnecting means rated 10 k AIR
minimum
22 kA
QO-VH (125 A, 2P, 40–125 A)
QO-VH (225 A, 2P, 40–60 A) [5]
LJL (125–400 A, 2P or 3P) [7]
Must be protected by an upstream disconnecting means rated 22 k AIR
minimum
25 kA
QD (225 A 2P or 3P, 70–225 A)
LJL (125–400 A, 2P or 3P) [7]
Must be protected by an upstream disconnecting means rated 25 k AIR
minimum
42 kA
QOH (125 A, 2P, 40–125 A)
QOH (225 A, 2P, 40–60 A) [5]
LJL (125–400 A, 2P or 3P) [7]
Must be protected by an upstream disconnecting means rated 42 k AIR
minimum
QO-VH (125 A, 2P, 40–125 A)
QO-VH (225 A, 2P, 40–60 A) [5]
QD (225 A 2P or 3P, 70–225 A)
Must be protected by a Square D circuit breaker Type LA (400 A max.) or
MA
(1000 A max.) Rated 42 k AIR minimum
65 kA
QG (225 A 2P or 3P, 70–225 A)
LJL (125–400 A, 2P or 3P) [7]
Must be protected by an upstream disconnecting means rated 65 k AIR
minimum
QO-VH (125 A, 2P, 40–125 A)
QO-VH (225 A, 2P, 40–60 A) [5]
QD (225 A 2P or 3P, 70–225 A)
LJL (125–400 A, 2P or 3P) [7]
Must be protected by a Square D circuit breaker Type LH (400 A max.);
MG or MJ (800 A max.); MH (1000 A max.); PG or PJ (1200 A max.); RG or
RJ (2000 A max.).
100 kA
QJ (225 A 2P or 3P, 70–225 A ) [6]
LJL (125–400 A 2P or 3P) [7]
Must be protected by an upstream disconnecting means rated 100 k AIR
minimum
QO-VH (125 A, 2P, 40–125 A)
QO-VH (225 A, 2P, 40–60 A) [5]
Must be protected by an upstream disconnection means with Class R (600
A max.); Class J (600 A max); Class T6 (800 A max.); Class T3 (1200 A
max.) or Class L (1200 A max.).
QD (225 A 2P only, 70–225 A)
LJL (125–400 A, 2P or 3P) [7]
QD (225 A 3P only, 70–225 A) [6]
Must be protected by an upstream disconnection means with Class R (600
A max.); Class J (600 A max); Class T6 (800 A max.); Class T3 (1200 A
max.) or Class L (1200 A max.) fuses or by a Square D circuit breaker Type
MJ (800 A max.); MHF (1000 A max.); PJ (1200 A max.); or RJ (2000 A
max.) rated 100 k AIR minimum.
EZ Meter-Pak—Main Circuit Breaker Applications—See Figure 3
10 kA
QO (125 A, 2P, 40–125 A)
400–2000 A EZM Main Device with Type LH (400 A max.); MG or MJ (800
A max.); MH (1000 A max); PG or PJ (1200 A max.); RG or RJ (2000 A
max.)
QO (225 A, 2P, 40–125 A) [5]
QB (225 A 2P or 3P, 70–225 A)
EZM Branch Units
Tenant
Circuit
Breakers
Transformer
Load
Centers
(Main Lugs)
EZM Circuit Breaker Main
or EZM Main Fusible Switch
Figure 3 [4]
65 kA
QO-VH (125 A, 2P, 40–125 A)
QO-VH (225 A, 2P, 40–60 A) [5]
QD (225 A 2P or 3P, 70–225 A)
LJL (125–400 A, 2P or 3P) [7]
100 kA
QO-VH (125 A, 2P, 40–125 A)
QO-VH (225 A, 2P, 40–60 A) [5]
QD (225 A 2P only, 70–225 A)
QD (225 A 3P only, 70–225 A) [6]
LJL (125–400 A, 2P or 3P) [7]
1000 A Main Device with catalog number suffix "CBU" supplied with Type
MHF circuit breaker.
QD (225 A 2P only, 70–225 A)
QD (225 A 3P only, 70–225 A) [6]
LJL (125–400 A 2P or 3P) [7]
800–2000 A EZM Main Device with Type MJ (800 A max.); MHF (1000 A
max.); PJ (1200 A max.) or RJ (2000 A max.)
EZ Meter-Pak—Main Fusible Switch Applications—See Figure 3
10 kA
QO (125 A, 2P, 40–125 A)
QO (225 A, 2P, 40–125 A) [5]
QB (225 A 2P or 3P, 70–225 A)
400–1200 A EZM Main Device (1Ø or 3Ø) with Class T (300 Vac) fuses
installed.
100 kA
QO-VH (125 A, 2P, 40–125 A)
QO-VH (225 A, 2P, 40–60 A) [5]
QD (225 A 2P, only, 70–225 A)
QD (225 A 3P only, 70–225 A) [6]
LJL (125–400 A, 2P or 3P) [7]
400–1200 A EZM Main Device (1Ø or 3Ø) with Class T (300 Vac) fuses
installed.
2
METERING EQUIPMENT
[1] Tenant circuit breakers of same frame size having higher AIR values may replace tenant circuit breakers as listed in this table and maintain the series rating.
[2] Meter center short circuit current rating is equal to the lowest short circuit current rating given in table for any circuit breaker installed in any meter panelboard in the meter center.
[3] Short circuit current rating is measured at the LINE SIDE terminals of the integral mounted or remote mounted main providing overcurrent protection for the EZM metering equipment lineup.
[4] For three-tier series ratings refer to Data Bulletin 4100DB0301 and Instruction Bulletin 80043-303-22.
[5] Requires use of EZM125QOA adapter (order separately).
[6] 3P only tenant circuit breaker(s) are limited to: 100 kA Max. at 208Y/120 Vac or 65 kA Max at 240/120 Vac.
[7] Supplied with factory-installed circuit breaker(s), with an adjustable trip range of 125–400 A.
5/15/2019