Technical Data Bulletin
Table Of Contents
- Section 1 Load Centers
- EZ Selector - Selection Assistance
- QO™ Miniature Circuit Breakers
- QO™ Load Centers
- Homeline™ Miniature Circuit Breakers
- Homeline™ Load Centers
- QO/Homeline Load Center Value Packs and Accessories
- QO/Homeline Load Center Dimensions
- Combination Service Entrance Devices
- Homeline Solar Ready PoN CSEDs
- Wiser Energy™ and Wiring Devices
- Enclosed Devices
- Servicepak™ Power Outlet Panels
© 2020 Schneider Electric
All Rights Reserved
12/02/2020
1-23
www.se.com/us
Homeline Load Centers, Indoor, 1Ø
Homeline™ Load Centers
Class 1170 / Refer to Catalog 1100CT0501
QOM2 Frame Size
100–225 Amperes
Table 1.53: QOM2 Frame Size—Use with Convertible Main Load Centers Only
Main Circuit Breaker
Rating [10]
Convertible
Load Center Mains
Rating
22 k AIR [11]
Lug Wire Size [12]
AWG/kcmil
Main Circuit Breaker [13]
100 A 150–225
QOM2100VH
4–300 Al or Cu
125 A 150–225
QOM2125VH
150 A 150–225
QOM2150VH
175 A 200–225
QOM2175VH
200 A 200–225
QOM2200VH
225 A 225
QOM2225VH
HOM Plug-on Neutral Load Center Main Breaker, Convertible
Mains (1Ø3W—120/240 Vac Indoor—UL Listed)
Table 1.54: Convertible Main Breaker Plug-on Neutral Load Centers (Compatible with HOM Plug-on Circuit Breakers and HOM Plug-on
Neutral Circuit Breakers)
Mains
Rating
Spaces
Max.
Single
Pole
Circuits [14]
Max.
Tandem
Circuit
Breakers
Load Center
Box, Interior and Cover [15]
Main Wire Size
AWG/kcmil
Equipment Ground
Bar Kit
(Order Separately)
Box No.
[16]
Al Cu
I
N
D
O
O
R
Main Circuit Breaker—22 kA Short Circuit Current Rating
Convertible Mains—Factory-installed Main Circuit Breaker
QOM1 Main Frame Size—Convertible to Main Lugs or Lower Amperage Main Circuit Breaker (See page 1-25)
100 A
8 16 8 HOM816M100PC 6–1 PK9GTA 5
12 24 12 HOM1224M100PC 6–2/0 PK15GTA 6
20 40 20 HOM2040M100PC 6–1 PK18GTA 7
24 48 24 HOM2448M100PC 6–2/0 PK23GTA 8
30 60 30 HOM3060M100PC 6–2/0 PK23GTA 10
125 A
24 48 24 HOM2448M125PC
6–2/0
6–1/0 PK23GTA 8
30 60 30 HOM3060M125PC 6–2/0 PK23GTA 10
Convertible Mains—Factory-installed Main Circuit Breaker
QOM2 Main Frame Size—Convertible to Main Lugs or Lower Amperage Main Circuit Breaker (See page 1-25)
150 A 30 60 30 HOM3060M150PC 4–250 PK23GTA 10
200 A
20 40 20 HOM2040M200PC
4–250
PK18GTA 9
30 60 30 HOM3060M200PC PK23GTA 10
40 80 40 HOM4080M200PC PK27GTA 12
42 84 42 HOM4284M200PC PK27GTA 12
60 120 60 HOM60120M200PC PK27GTA 25
225 A 42 84 42 HOM4284M225PC 4–300 4–250 PK27GTA 12
Split Bus Plug-on Neutral Load Center—Manual Transfer for use with Temporary Backup Power Source Applications NEMA 1 (indoor)
200 A 36 72 36 HOM1428X2244M200PC 4–250 PK27GTA 12
Above listings through 200 A mains rating meet Federal Specification W-P-115c as Type 1, Class 2.
1
LOAD CENTERS
[10] Do not exceed the load center mains rating.
[11] 22 k AIR main circuit breaker UL Listed for use ahead of QO, QOT and QO-PL 10 k AIR branch circuit breakers to permit their application on systems with up to 22 kA available fault current.
[12] Wire range listed for QOM circuit breaker kits is the wire range of that circuit breaker. To find out maximum wire size permitted in a particular load center per UL, see Main Wire Size in that
load center table.
[13] Add suffix 1021 for 120, 208 or 240 Vac shunt trip.
[14] Maximum single pole branch circuits utilizing HOM and/or HOMT circuit breakers.
[15] C at end of catalog number indicates combination flush/surface cover included with device.
[16] See page 1-31